B F

John B.

Is a pressure difference from 1.2 bar cold to 2 bar at 48°C normal for a Vitodens 333 heating system?

For the Vitodens 333, the minimum required installation pressure is 0.8 bar and the maximum permitted service pressure is 3 bar; the safety valve is set to 3 bar. A rise from 1.2 bar cold to 2.0 bar at 48°C is explained by thermal expansion of the water and remains within the safe range as long as pressure stays below 3 bar. However, an increase of 0.8 bar at only 48°C may indicate that the expansion vessel (12 L, precharged to 0.75 bar nitrogen) needs its nitrogen precharge checked, or that an additional vessel is needed if the total water volume of the installation is large.

B F

John B.

Is a pressure increase from 1.2 bar (cold) to 2.0 bar (at 48 °C) normal for a heating boiler?

Yes, a pressure increase caused by thermal expansion during water heating is normal. As long as the pressure stays between the minimum operating limit (0.8 bar) and the maximum safety threshold (3 bar), the system operates within safe parameters. If the pressure variation is excessive, check the expansion vessel pressure.