What could be the cause of experiencing regular interruptions with the MiCOM device?
Misconfigured overcurrent, earth fault, or minimum current thresholds can cause unwanted trips. Too short timings can lead to rapid trips in the event of a transient fault. Poorly configured automation functions, such as the recloser, can cause unwanted interruption/recovery cycles. External signals via the logic inputs can cause trips if these inputs are misconfigured or subject to disturbances. It is necessary to carefully analyze the configuration of these different elements and check whether external events are likely to cause these trips.