What causes a frozen level reading, and how can it be resolved?

A frozen level reading is typically caused by parasitic signal interference or build-up on the probe. Perform background echo suppression or clean the probe. If the reading remains frozen after manual suppression, ensure the actual level echo was not masked by mistake, verify that the suppression end distance does not exceed the product distance, or reset the mapping curve.

J A

Jennifer J.

What should be done if the level measurement remains frozen after performing a manual echo suppression?

Verify that the end suppression distance does not exceed the actual product distance. If the level echo was accidentally suppressed, reset the mapping curve using the 'Delete curve' or 'Factory map' option in the distance confirmation menu, or re-record the suppression. Temporarily disabling echo tracking can also help restore the signal.