WM14DINAV63HR2XXAX | WM14DINAV63HO2S1AX | WM14DINAV63HO2XXAX | WM14DINAV63LO2S1AX | WM14DINAV63LO2XXAX | WM14DINAV63HXXS1AX | WM14DINAV63HXXXXAX | WM14DINAV53LR2S1AX | WM14DINAV53LR2XXAX | WM14DINAV53LO2S1AX | Installation manual | CARLO GAVAZZI WM14DINAV63HR2S1AX Guide d'installation

Add to My manuals
4 Pages
WM14DINAV63HR2XXAX | WM14DINAV63HO2S1AX | WM14DINAV63HO2XXAX | WM14DINAV63LO2S1AX | WM14DINAV63LO2XXAX | WM14DINAV63HXXS1AX | WM14DINAV63HXXXXAX | WM14DINAV53LR2S1AX | WM14DINAV53LR2XXAX | WM14DINAV53LO2S1AX | Installation manual | CARLO GAVAZZI WM14DINAV63HR2S1AX Guide d'installation | Fixfr
SETUP OUT2
WM14DIN A/WM1496 A
Instrument instruction sheet
OUT1 or OUT2
Three Phase power analyser
S
Measuring mode
S
SETUP ALARMS
d
0...100 (%)
RESET
S
S
S
S
S
S
1...32
RESET
S
S
S
S
S
S
1...255
RESET
S
S
S
S
S
S
4,8 - 9,6 - 19,2 - 38,4
0...999
S
S
Uncorrect password
S
S
Correct password
S
S
Main menu
S
0...999
S
S
S
S
S
S
3P.n- 3P.1 - 3P.A - 3P - 2P - 1P
S
S
S
S
Measuring mode
1
1...999
S
S
E
W dmd max
A dmd max
A1 max
A2 max
A3 max
WL1 max
WL2 max
WL3 max
VL1 max
VL2 max
VL3 max
PF1 min
PF2 min
PF3 min
A1 min
A2 min
A3 min
VL1 min
VL2 min
VL3 min
1.0...99.9
S
F
S
S
S
■ RESET AND ACCESS TO THE MAIN MENU
S.rE : resets all minimum and maximum stored values
(see table “F”).
P.rE : resets all maximum stored values (see table “E”).
E.P.r: resets kvarh/kWh partial counters.
PAS : if you enter the correct password (the default password is 0) you access to the main menu.
■ THE MAIN MENU FUNCTIONS
n_P : new password, change password function.
SYS : electrical system, choose the correct electrical
system; 3P.n: 3-phase unbalanced with or without neutral;
3P.A: 3-phase ARON; 3P: 3-phase balanced without neutral;
3P.I: 3-phase balanced with neutral (requires only one voltage input “VL1-N” and one current input “I1)”; 2P: twophase, 1P: single phase.
Ct.r : CT ratio, “dP” selects the position of the decimal
point and the of the “k” or “M” multiplyer. “Ct.r” selects
the required CT value from 1 to 999.
Example: if the primary of the CT being connected is 300kA
and the secondary is 5A, the CT ratio corresponds to 60,0k
(obtained from the calculation: 300000/5).
Ut.r : VT ratio. “dp” selects the decimal point position
and the VT ratio “k” or “M” multiplyer .
“Ut.r” selects the required VT ratio from 1 to 999.
Example: if the primary of the VT being connected is
5kV and the secondary is 100V, the VT ratio will be 50
(given by 5000/100).
P.i.t. : integration time for the calculation of power dmd:
select the required value from 1 to 30 minutes.
A.i.t: current integration time of thermical current: select
the required value from 1 to 30 minutes.
thd : selects whether to activate (YES) or deactivate
(NO) the harmonic analysis.
ou.1 / ou.2 : selects the type of output among: pulses,
alarm or remote control. See the relevant instructions
on the following page.
SEt : setting of alarm output parameters. See the relevant instructions on the following page.
Fis : filtering range programming to set the operating
range of the digital filter. The value is expressed as % of
the full scale value.
Fic : selection of filtering coefficient value from 1 to 32.
Increasing the value, also the stability and the settling
time of the measurements are increased.
Adr : instrument serial port address: from 1 to 255.
Bdr : baudrate selection (38.400; 19.200; 9.600; 4.800).
H.rE: reset of the hour counter.
E.tr: reset of the total and partial energy counters.
End : to confirm the new selected values press the S key,
or press ▲ ▼ to remain in the programming menu.
■ RESET E ACCESSO AL MENÙ PRINCIPALE
S.rE : azzera tutti i valori minimi e massimi memorizzati
(vedi tabella “F”).
P.rE : azzera i valori massimi memorizzati (vedi tabella “E”).
E.P.r : azzera i contatori kvarh/kWh parziali.
PAS : inserendo il valore di password corretto (di default
0) si accede al menù principale.
■ LE FUNZIONI DEL MENÙ PRINCIPALE
n_P : nuova password, personalizza la password.
SYS : sistema elettrico, scegliere il sistema elettrico corretto: 3P.n: trifase sbilanciato con o senza neutro, 3P.A: trifase
ARON, 3P: trifase bilanciato senza neutro, 3P.I: trifase bilanciato con neutro (richiede un solo ingresso voltmetrico
“VL1-N” e un ingresso amperometrico “I1”), 2P: bifase, 1P:
monofase.
Ct.r : rapporto TA. “dP” seleziona la posizione del punto
decimale e il moltiplicatore del rapporto TA “k” o “M”.
“Ct.r” seleziona il valore del rapporto TA richiesto da 1 a
999. Esempio: se il primario del TA ha una corrente di
300kA e il secondario di 5A, il rapporto TA corrisponde a
60,0k (ottenuto eseguendo il calcolo: 300000/5).
Ut.r : rapporto TV. “dP” seleziona la posizione del punto
decimale e il moltiplicatore del rapporto TV “k” o “M”.
“Ut.r” seleziona il valore TV richiesto da 1 a 999.
Esempio: se il primario del TV connesso è di 5kV e il
secondario è di 100V il rapporto di TV corrisponde a 50
(ottenuto eseguendo il calcolo: 5000/100).
P.i.t: tempo di integrazione per il calcolo della potenza
media: selezionare il tempo desiderato da 1 a 30 minuti.
A.i.t: tempo di integrazione per il calcolo della corrente
termica: selezionare il valore desiderato da 1 a 30 minuti.
thd : seleziona se attivare l’analisi armonica (YES) o disattivare l’analisi armonica (no).
ou.1 / ou.2 : selezione del tipo di uscita: impulsi, allarme o
remoto. Vedere le istruzioni dedicate nella pagina seguente.
SEt : impostazioni parametri uscita allarme. Vedere le
istruzioni dedicate nella pagina seguente.
Fis : selezione del campo di intervento del filtro digitale
espresso in % del valore di fondo scala.
Fic : selezione del coefficiente di filtraggio da 1 a 32.
Aumentando il coefficiente aumenta la stabilità e il tempo
di assestamento delle misure.
Adr : indirizzo seriale: da 1 a 255.
Bdr : seleziona la velocità di trasmissione dati (38.400;
19.200; 9.600; 4.800).
h.rE: azzeramento del conta ore.
E.tr: azzeramento dei contatori di energia totali e parziali.
End : per confermare i dati impostati e tornare al modo
misura premere S , o ▲ ▼ per restare nel menù di
programmazione.
■ RÜCKSETZEN UND DAS HAUPTMENÜ AUFRUFEN
S.rE : rücksetzen aller gespeicherten Mindest. und Max. Werte
(siehe Tafel “F” ).
P.rE : rücksetzen aller gespeicherten max. Werte (siehe Tafel “E”).
E.P.r : rücksetzen der kvarh/kWh Teilzähler.
PAS : Wenn Sie das richtige Passwort eingeben, gelangen Sie
in das Hauptmenü (das Standard-Passwort ist 0) .
■ DIE FUNKTIONEN DES HAUPTMENÜS
n_P : Neues Passwort, Passwortfunktion ändern.
SYS : Wahl der korrekten Systemart: 3P.n: unsymmetrische Last,
3Phasen mit oder ohne Nulleiter; 3P.A: 3-Phasig ARON, 3P: 3Phasig symmetrische Last ohne Nulleiter; 3P.I: 3-Phasig symmetrische mit Nulleiter (nur ein Spannungseingang “VL1-N” und ein
Stromeingang “I1” notwendig), 2P: 2-Phasig, 1P: 1-Phasig.
Ct.r: Stromwandler Verhältnis; “dP” Wahl der
Dezimalpunktposition und “k” oder “M” als Multiplikators
des Stromwandler Verhältnis; “Ct.r” Wahl des
Stromwandlerverhältnisses von 1 bis 999.
Beispiel: Bei dem Primärstrom des Wandlers von
300kA und einem Sekundärstrom 5A ergibt sich das
Verhältnis zu 60,0k (Quotient 300000/5).
Ut.r: Spannungswandler Verhältnis; “dP” Wahl der
Position des Dezimalpunktes und “k” oder “M” als
Multiplikators des Spannungswandler Verhältnis. “Ut.r”
Wahl des Spannungswandlerverhältnisses von 1 bis 999.
Beispiel: Bei einer Primärspannung des Wandlers von 5
kV und einer Sekundärspannung 100 V, ergibt sich das
Verhältnis zu 50 (Quotient 5000 V/100 V).
P.i.t. : Integrationszeit der Leistung dmd: Wert zwischen
1 und 30 Minuten wählen.
A.i.t: Integrationszeit für Stromintegral: wählen sie den
gewünschten Wert von 1 bis 30 Minuten.
thd : Wahl ob das harmonische Analyse aktivierien (YES)
oder deaktivieren (no).
ou.1 / ou.2 : Wahl des Ausgangstyp: Impuls, Alarm oder
Schaltausgang. Siehe Anleitungen auf folgenden Seiten.
SEt : Einstellungen Parameter Alarmausgang. Siehe
Anleitungen auf folgenden Seiten.
Fis : Arbeitsbereich des Digitalfilters wählen. Der Wert
wird in % vom Vollbereichs-wert angegeben.
Fic : Filterkoeffizient von 1 bis 32 wahlen. Bei einem größeren Wert erhöhen sich auch die Stabilität und die
Einstellzeit für die Messungen.
Adr : Adresse der seriellen Schnittstelle zwischen 1 und
255 einstellen.
Bdr : Wahl von Baudrate (38.400; 19.200; 9.600; 4.800).
H.rE: Rücksetzen der Stundenzähler.
E.tr: Rücksetzen der Teil und Gesamt -Energiezähler.
End: Ende: neuen Wert durch Drücken von S bestätigen oder durch ▲ ▼ Drücken im Hauptmenü bleiben.
WARNING: if
WARNING: if VLN x IL x Ct.r x Ut.r x 3 ≥ 999.999.999 (999M),
the instrument displays “Err” . VLN: phase-neutral line voltage or VT seconday voltage. IL: CT secondary current. Ct.r: CT
ratio. Ut.r: TV ratio.
ATTENZIONE: se VLN x IL x Ct.r x Ut.r x 3 ≥ 999.999.999
(999M), lo strumento indica “Err” . VLN: tensione fase-neutro dell’impianto (VLN), oppure del secondario TV. IL: corrente secondario del TA . Ct.r: rapporto TA. Ut.r: rapporto TV .
WARNUNG: erreicht VLN x IL x Ct.r x Ut.r x 3 den Wert:
999.999.999 (999M), ist die Anzeige “Err”. VLN: NetzPhasen-Neutralsspannung oder Sekundärspannung der
Spannungswandler; IL: Sekundärstrom;
Ct.r: Stromwandlersverhältnis
Ut.r: Spannungswandlersverhältnis.
S
SYS= 3p.n
V
k
A
M
L
1
VA
▲
S
Hz
al
al
Hz
al
▲
h
Hz
M
al
▲
A
M
L
1
al
▲
Hz
A
M
L
1
al
▲
var
Hz
k
A
M
L
1
al
▲
h
Hz
al
▲
h
var
L
3
Hz
PF dmd
Phase sequence: 123 or 132
k
M
W
L
2
var
L
3
V
A
VA
W
L
2
PF dmd
Asymmetry V LL
fig. 9
V
VA
h
L
3
PF dmd
V12, V23, V31
k
W
L
2
var
ATENCIÓN: si VLN x IL x Ct.r x Ut.r x 3 ≥ 999.999.999 (999M),
el equipo visualiza “Err” . VLN: tensión de línea fase-neutro o
tensión del secundario del trafo de tensión. IL: intensidad del
secundario del trafo de intensidad. Ct.r: relación del trafo de
intensidad. Ut.r: relación del trafo de tensión.
fig. 8
V
VA
h
L
3
PF dmd
V LL sys, PF sys
k
W
L
2
var
Hz
fig. 7
V
VA
h
L
3
PF dmd
V LN sys, PF sys
A
L
1
W
L
2
var
L
3
k
■ LAS FUNCIONES DEL MENÚ PRINCIPAL
n_P : nueva clave, función de cambio de clave.
SYS : selección del sistema eléctrico adecuado: 3P.n: sistema trifásico, carga desequilibrada con o sin neutro, 3P.A: trifásico ARON, 3P: sistema trifásico, carga equilibrada sin
neutro, 3P.I: sistema trifásico, carga equilibrada con neutro
(necesita de una sola entrada de tensión “VL1-N” y una
entrada de intensidad “I1”), 2P: sistema bifásico, 1P: sistema monofásico.
Ct.r : relación del trafo de intensidad (CT); “dP” selección del
punto decimal y el multiplicador “k” o “M” del trafo de intensidad. “Ct.r” selecciona el valor del trafo de intensidad necesario de 1 a 999. Ejemplo: si el primario del CT conectado
es de 300kA y el secundario de 5A, la relación del CT será
60,0k (cantidad obtenida del cálculo: 300000/5).
Ut.r : relación del trafo de tensión (VT). “dP” selecciona el
punto decimal y el multiplicador “k” o “M” del trafo de tensión. “Ut.r” selecciona el valor del trafo de tensión de 1 a
999. Ejemplo: si el primario del VT conectado es de 5kV y el
secundario es 100V, la relación del VT será 50 (resultante de
5000/100).
P.i.t. : tiempo de integración para el cálculo de la potencia dmd:
selección del valor deseado de 1 a 30 minutos.
A.i.t: tiempo de integración para el cálculo de la intensidad
térmica: seleccionar el valor deseado de 1 a 30 minutos.
thd : selección de la activación (YES) o desactivación (NO)
del análisis de armónicos.
ou.1 / ou.2 : selección tipo de salida: pulsos, alarma o remota. Leer las instrucciones en la pagina siguente.
SEt : ajuste parámetros salida alarma. Leer las instrucciones
en la pagina siguente.
Fis : programación del rango de filtrado para ajustar la escala
operativa del filtro digital. Se expresa en % del valor de la escala completa.
Fic : Selección del coeficiente de filtrado desde 1 hasta 32. A medida que aumenta este valor, aumenta también la estabilidad y el
tiempo de respuesta de las medidas.
Adr : dirección del puerto serie del instrumento: de 1 a 255.
Bdr : selección de la velocidad en baudios de transmisión
datos (38.400; 19.200; 9.600; 4.800).
H.rE: puesta a cero del contador horario.
E.tr: puesta a cero de los contadores de energía totales y parcial.
End : para confirmar los nuevos valores seleccionados y volver al modo medida pulse S , o para restar en las funciones del menú de programación pulse ▲ ▼ .
ATTENTION: si VLN x IL x Ct.r x Ut.r x 3 ≥ 999.999.999
(999M), l’appareil affiche “Err” . VLN: tension de ligne phaseneutre ou tension du secundaire TT; . IL: courant secundaire
du TC. Ct.r: ratio TC; Ut.r: ratio TT .
fig. 6
V
VA
W
L
2
PF dmd
V L1, V L2, V L3
M
k
M
L
1
VA
L
2
▲
W
h
L
3
var
Hz
al
PF dmd
An, Hz
fig. 12
V
k
A
M
L
1
VA
L
2
▲
To next page
Alla pagina succesiva
Zu folgende Seite
A la page suivante
A la página siguiente
fig. 11
V
A
▲
W
h
L
3
var
Hz
al
PF dmd
W1, W2, W3
L
2
k
A
M
L
1
▲
W
var
Hz
V
k
A
M
L
1
VA
h
L
3
fig. 14
fig. 13
V
VA
▲
SETUP ALARMS
L
1
L
2
▲
SETUP OUT2
fig. 10
al
W1 dmd, W2 dmd, W3 dmd
▲
W
h
L
3
var
Hz
al
PF dmd
PF dmd
PF 1, PF 2, PF 3
fig. 15
V
k
al
PF dmd
A L1, A L2, A L3
A
M
fig. 16
L
1
L
2
▲
W
h
L
3
var
Hz
al
PF dmd
var L1, var L2, var L3
V
k
A
M
L
1
VA
VA
▲
c
▲
var
L
3
A
L
1
VA
h
var
k
■ PUESTA A CERO Y ACCESO AL MENÚ PRINCIPAL
S.rE : puesta a cero de los valores min. y max. almacenados
(veer tabla “F”).
P.rE : puesta a cero de los valores max. almacenados (ver
tabla “E”).
E.P.r : puesta a cero de los contadores kvarh/kWh parciales.
PAS : al introducir la clave correcta (la clave por defecto es
0), se accede al menú principal.
A L1 dmd, A L2 dmd,
A L3 dmd
SETUP OUT1
OUT1 or OUT2
S
M
fig. 5
V
▲
h
L
3
var
Hz
al
PF dmd
VA L1, VA L2, VA L3
fig. 17
V
k
A
M
L
1
L
2
▲
W
h
L
3
var
Hz
al
PF dmd
VA sys, W sys, var sys
fig. 18
V
k
A
M
L
1
VA
VA
W
L
2
▲
S
A
L
1
▲
b
k
W
L
2
PF dmd
Asymmetry V LN
S
▲
Hz
V
VA
h
L
3
PF dmd
a
M
W
L
2
var
L
3
A
L
1
▲
h
S
k
▲
▲
fig. 4
fig. 3
V
VA
W
L
2
S
fig. 2
1
▲
S
L
1
▲
fig. 1
S
S
ESPAÑOL
■ FUNCIONES DEL TECLADO
S Permite entrar en el modo de programación y confirmar el valor programado.
▲ En el modo de medida: para desplazarse a la siguiente variable visualizada. En el modo de programación: para desplazarse a la
siguiente función o para aumentar el valor del parámetro.
▼ En el modo de medida: para desplazarse a la última variable
visualizada. En el modo de program.: para desplazarse a la última
función o reducir el valor del parámetro.
■ REMISE À ZÉRO ET ACCÈS AU MENU PRINCIPAL
S.rE : remise a zéro de tous les valeurs min, et max.
mémorisées (voir table “F”).
P.rE : remise a zéro de tous les valeurs maxi mémorisées
(voir table “E”).
E.P.r : remise a zéro de tous les compteurs kvarh/kWh partiels.
PAS: la saisie du mot de passe correct (0 par défaut) donne
accès au menu principal.
■ FONCTIONS DU MENU PRINCIPAL
n_P: fonction nouveau mot de passe, fonction changer mot
de passe.
SYS : réseau électrique, choisir le réseau électrique correct:
3P.n: 3-Phases charge non équilibrée avec ou sans neutre;
3P.A: 3-Phases ARON; 3P:3-Phases équilibré sans neutre,
3P.I: 3-Phases équilibré avec neutre (avec seulement une
entrée du tension “VL1-N” et une entrée de courant “I1”),
2P: 2-Phases, 1P: 1-Phase.
Ct.r : ratio du transformateur de courant “dP” sélection du
point decimal et le multiplicateur “k” ou “M” du transformateur de courant “Ct.r”; sélection du ratio du transformateur
de courant de 1 à 999. Exemple: si le primaire du TC raccordé est de 300kA et si le secondaire est de 5A, le ratio TC
correspond à 60,0k (soit 300000 divisé par 5) .
Ut.r : ratio du transformateur de tension. “dP” sélection du
point decimal et le multiplicateur “k” ou “M” du transformateur de tension. “Ut.r” sélection de la valeur du transformateur de tension de 1 à 999. Exemple: si le primaire du TT
raccordé est de 5kV et si le secondaire est de 100V, le ratio
TT sera de 50 (soit 5000 divisé par 100).
P.i.t.: temps d'intégration pour le calcule de la puissance
dmd: sélectionner la valeur nécessaire entre 1 et 30 minutes.
A.i.t: temps d'intégration pour le calcule du courant thermique: sélectionner la valeur désirée de 1 à 30 minutes.
thd : sélection si activer l’analyse harmonique (YES) ou la
desactiver (no).
ou.1 / ou.2 : sélection type de sortie: impulsions, alarme ou
remote.
Voir les instructions à la page suivante.
SEt : réglages paramètres sortie alarme. Voir les instructions
à la page suivante.
Fis: la programmation de la gamme de filtrage permet de définir la plage de fonctionnement du filtre numérique. La valeur est
exprimée en pourcentage de la valeur en échelle totale.
Fic: sélection de la gamme de filtrage de 1 à 32. Lorsqu'on augmente cette valeur, on augmente également la stabilité et le
temps de stabilisation des mesures augmente également.
Adr: Adresse du port série: de 1 à 255.
Bdr : sélection de debit baud de données (38.400; 19.200;
9.600; 4.800).
H.rE: remise à zéro des compteurs horaires
E.tr: remise à zéro des compteurs d’énergie totales et partiels.
End: pour confirmer les nouvelles valeurs sélectionnées,
appuyer sur la touche S , ou appuyer sur la touche ▲ ▼
pour revenir aux fonctions du menu de programmation.
L
2
▲
S
VA dmd max
FRANÇAIS
■ FONCTIONS CLAVIER
S Accès à la phase programmation et confirmation des
valeurs.
▲ En mode mesure: affiche la variable suivante. En mode
programmation: affiche la fonction suivante ou augmente la
valeur du paramètre.
▼ En mode mesure: affiche la variable précédente. En
mode programmation: affiche la fonction précédente ou
diminue la valeur du paramètre.
▲
W
h
L
3
L
2
▲
S
DEUTSCH
■ TASTENFUNKTIONEN
S Programmiermodus aktivieren und eingegebenen Wert
bestätigen.
▲ Im Meßodus: zur nächsten anzuzeigenden Netzgröße
‘blättern’. Im Programmiermodus: zur nächsten Funktion
‘blättern’ oder den Parameterwert erhöhen.
▼ Im Meßmodus: Zur vorherigen anzuzeigenden Netzgröße
‘blättern’. Im Programmiermodus: Zur vorherigen Funktion
‘blättern’ oder den Parameterwert verringern.
var
Hz
al
•
k
M
VA
▲
W
••
h
L
3
PF dmd
VA dmd, W dmd, Hz
V
A
var
Hz
al
PF dmd
MAX: V, A(•), W(••)
▲
1
ITALIANO
■ FUNZIONI DELLA TASTIERA
S Accede al modo programmazione e conferma i valori selezionati.
▲ Nel modo misura: passa alla visualizzazione della
pagina misura successiva. Nel modo programmazione:
passa alla funzione successiva o incrementa i valori.
▼ Nel modo misura: passa alla visualizzazione della
pagina misura precedente. Nel modo programmazione:
passa alla funzione precedente o decrementa i valori.
▲
S
WM14DIN/96 A IM ML 200508 Cod. 8020688
ENGLISH
■ KEY PAD FUNCTIONS
S Access to the programming phase and value confirmation.
▲ On measuring mode: scroll to the next displayed
system variable. On programming mode: scroll to the
next function or parameter value increase.
▼ On measuring mode: scroll to the previously displayed system variable. On programming mode: scroll to
the previous function or parameter value decrease.
▲
C o m p o n e n t s
▲
A u t o m a t i o n
▲
Carlo Gavazzi Controls SpA,
Via Safforze, 8 - 32100
Belluno (Italy)
Tel. +39 0437 931000,
Fax +39 0437 931021
CARLO GAVAZZI
2
S
S
S
S
■ ALARM SETUP MENU
A.O1 : “oFF” disables the alarm A.01, moving to the
next one (up to A.16). Any other previously selected
setting remains stored. “on” enables the alarm, then
select the variable to be controlled:
VAr : select the variable to be controlled (see table “ I”).
no, to go straight to the settings of the next alarm.
YES, to continue the programming of all other parameters relating to the alarm being set:
d.P.o : disable the alarm at power on, “no” to disable
the function or “YES” to enable it.
tYP : select the alarm type: up (uP) or down (do),
in window alarm (in), out window alarm (out).
dP : select the position of the decimal point.
Lo.S : select the value of the low setpoint.
Hi.S : select the value of the high setpoint.
dEL : select the delay time on activation from 0 to
255 seconds.
S
S
S
S
S
S
S
S
S
S
S
S
S
ALARM TYPE
UP
DO
IN
OUT
1.11
9.99
11.1
99.9
111
999
1.11K
9.99K
11.1 K
99.9K
111K
999K
1.11M
S
S
MAX VALUE
DECIMAL POINT
S
S
9.99M
11.1M
99.9M
111M
999M
Fun : select the OR or AND function (see the
“OR/AND” picture below)
out : select the relay to be enabled in case of alarm.
“rl.1” relay output 1 or “rl.2” relay output 2.
d
S
S
S
S
S
S
IMPORTANT NOTES:
• The measured variable blinks when an alarm occurs
(see figure “G” on the left: VL1, 200V). It’s possible to
link more than one alarm to the same variable, the
first alarm condition will make the variable range
blink. The “al” (•) LED shows the activation of one of
the two outputs (relay or open collector output) in
case they are selected as alarm.
• When both digital outputs are installed in the instrument
(relay or open collector), it’s possible to manage up to 16
alarms that can be linked to output 1 and/or output 2.
• If “var” or “W are negative, the decimal point on the very
right blinks in correspondence with the negative variable
(see figure “H” on the left).
• If the instrument displays a negative power, the relevant energy will not be counted.
G
L
1
V
k
A
M
■ SAFETY PRECAUTIONS
Carefully read the instruction manual. If the instrument is used in a way which is not specified
by the builder,the protection may be impaired.
Maintenance: To keep the intrument clean,use
a damp cloth; do not use abrasives or solvents. We
suggest you to disconnect the instrument before cleaning it.
VA
d
W
L
2
!
h
var
I
al
•
PF dmd
r
H
r31 Asy LN
r02 V L2
r17 var L1
r32 Asy LL
r03 V L3
r18 var L2
r33 A L1 dmd
r04 V L1-2
r19 var L3
r34 A L2 dmd
r20 Ph seq
r35 A L3 dmd
A
M
r06 V L3-1
r21 PF L1
r36 W L1 dmd
r07 A L1
r22 PF L2
r37 W L2 dmd
r08 A L2
r23 PF L3
r38 W L3 dmd
r09 A L3
r24 V LN sys
r39 VA L1 dmd
r10 A n
r25 V LL sys
r40 VA L2 dmd
r11 W L1
r26 W sys
r41 VA L3 dmd
al
r12 W L2
r27 VA sys
r42 W sys dmd
PF dmd
r13 W L3
r28 var sys
r43 VA sys dmd
r14 VA L1
r29 PF sys
r15 VA L2
r30 Hz
var
Hz
fig. 20
fig. 19
▲
2
•
V
k
A
M
▲
W
var
Hz
al
PF dmd
MIN: V, A(•)
L
2
k
A
M
-
L
1
▲
W
var
Hz
VAr
d.P.o
tYP
dP
Lo.S
HI.S
dEL
Fun
out
k
A
M
L
1
L
2
al
PF dmd
PF 1 - PF 2 - PF 3 - MIN
▲
W
var
Hz
■ PRECAUZIONI DI SICUREZZA
Leggere attentamente il manuale di istruzioni. Qualora
l’apparecchio venisse adoperato in un modo
non specificato dal costruttore, la protezione
prevista dall’apparecchio potrebbe essere compromessa. Manutenzione: Per mantenere pulito lo strumento usare un panno inumidito; non usare abrasivi o
solventi. Si consiglia di scollegare lo strumento prima di
eseguire la pulizia.
!
L
2
8
al
L
3
VA dmd MAX, W dmd MAX
k
A
M
■ SICHERHEITSMAßNAHMEN
Die Betriebsanleitung aufmerksam lesen. Sollte das
Gerät nicht gemäß der Herstellerangaben verwendet werden, könnte der vom Gerät vorgesehene Schutz beeinträchtigt werden.
Wartung: Das Gerät mit einem feuchten Tuch reinigen;
keine Scheuer- oder Lösemittel verwenden. Das Gerät
vor der Reinigung ausschalten.
!
fig. 24
L
1
▲
W
L
2
var
Hz
al
•
V
k
A
M
L
3
L
1
VA
▲
W
var
Hz
L
2
k
A
M
• La variable mesurée clignote indiquant l’activation
d’une alarme (voir figure “G” à gauche: VL1, 200V).
Une ou plusieurs alarmes peuvent être connectées à
la même variable, la première condition d’alarme fait
clignoter la gamme de la variable. L’activation d’une
des deux sorties (relais ou collecteur ouvert) est indiqué par le diode “al” (•) s’elles sont sélectionnées
comme alarme.
■ MENU AJUSTE DE ALARMA
A.O1 : “oFF” desactiva la alarma A.01, y continua a la alarma siguente (hasta A 16). Todos los ajustes seleccionados anteriormente permanecen en memoria.
“on” permite la habilitación de la alarma, después seleccionar la variable que debe ser controlada:
VAr : seleccionar la variable que debe ser controlada (ver
tabla “I”). no, para ajustar directamente la alarma
siguente.
YES, para continuar la programación de todos los
parámetros conectados a la alarma seleccionada:
d.P.o : desactivar la alarma al arranque, “no” para
desactivar la función o “YES” para activarla.
tYP : selecciona el tipo de alarma: de máximo (uP) o
de mínimo (do) alarma dentro de banda (in), alarma
fuera de banda (out).
dP : selección de la posición del punto decimal.
Lo.S : selección del limite mínimo.
Hi.S : selección del limite máximo.
dEL : selección del retardo a la conexión (0 a 255 s).
Fun : selección de la función de OR o AND (ver tabla
“AND/OR” abajo).
out : selección del relé que debe ser activado en
caso de alarma “rl 1” salida relé 1 o “rl.2” salida relé 2.
NOTAS IMPORTANTES:
• La variable medida parpadea en relación a una alarma
(ver figura “G” a la izquierda: V L1, 200V). Es posible
conectar mas de una alarma a la misma variable, el
campo variable parpadea en relación a la primera alarma. El LED “al” (•) indica la activación de una de las
dos salidas (relé o a colector abierto) si son seleccionadas como alarma.
• Si las dos salidas digitales (relé o a colector abierto)
están instaladas en el equipo es posible la gestión de
hasta 16 alarmas que pueden ser conectadas a la salida
1 y/o 2.
• Si “var” o “W” son negativos, el punto decimal a la
derecha parpadea en correspondencia a la variable
negativa (ver figura “H” a la izquierda).
• Si el equipo indica una potencia negativa, la energía
correspondiente no será calculada.
• Quand les deux sorties (relais ou collecteur ouvert) sont
installées dans l’appareil, on peut gérer jusqu’à 16 alarmes que peuvent être connectées à la sortie 1 et/ou 2.
• Si “var” ou “W sont négatives, le point décimal à droite
clignote en correspondance avec la variable négative (voir
figure “H” à gauche.
• Si l’appareil affiche une puissance négative, l'énergie
correspondante ne serait pas considerée.
■ MESURES DE SECURITE
Lire attentivement le manuel de l’utilisateur.
Si l’appareil est utilisé dans des conditions
differentes de celles spécifiées par le fabricant, le niveau de protection prévu par l’instrument
peut être compromis.
Entretien: Pour nettoyer l’instrument, utiliser un chiffon
humide; ne pas utiliser d’abrasifs ou de solvants. Il faut
déconnecter le dispositif avant de procéder au nettoyage.
■ NORMAS DE SEGURIDAD
Leer el manual y seguir atentamente las
instrucciones. Si se utiliza el equipo de manera distinta de como indica el fabricante se
puede dañar la protección de la que esta provisto el instrumento. Mantenimiento: para tener el instrumento
limpio, limpiar periódicamente la carcasa con un trapo
un poco humedecido. No utilizar productos abrasivos o
disolventes. Desconectar el instrumento antes de limpiarlo.
!
L
1
al
L
3
▲
W
var
Hz
al
PF dmd
h: 49 672.95
fig. 26
V
k
A
M
L
1
VA
h
PF dmd
THD: V, A(•)
fig. 25
V
VA
h
PF dmd
A dmd MAX
REMARQUES IMPORTANTES:
■ MENU RÉGLAGE ALARME
A.O1 : “oFF” désactivation de l’alarme A.01, en passant à
l’alarme suivante (jusqu’à A 16). Tous les autres réglages restent mémorisés. “on”: activation de l’alarme,
puis sélectionner la variable à contrôler:
VAr : sélectionner la variable à contrôler (voir table “ I”).
no, pour aller directement au réglage du prochaine alarme.
YES, pour continuer la programmation de tous les autres paramètres concernant l’alarme sélectionné:
d.P.o : desactiver l’alarme à l’allumage, “no” pour
desactiver la fonction ou “YES” pour l’activer.
tYP : sélectionner le type d’alarme: haute (uP) ou
basse (do), alarme dans fenêtre (in), alarme fenêtre
exterieure (out).
dP : sélection de la position du point décimal.
Lo.S : sélection valeur du point de consigne basse.
Hi.S : sélection valeur point de consigne haute.
dEL : sélection sur temporisation activée de 0 à 255 sec.
Fun : sélection fonction OR ou AND (voir la figure
“OR/AND” dessous).
out : sélection du relais à activer en cas d’alarme
Sortie relais 1 “rl.1”. Sortie relais 2 “rl.2” .
ou.1 / ou.2 : ajuste salida 1 / 2, selección:
EnE : retransmisión del valor de la energía activa “Act”
o reactiva “reA” mediante pulsos. “dP” selecciona el
punto decimal.
“PuL” selecciona el numero de pulsos para kWh/kvarh
de 0,01 a 500.
ALr : activa la salida de alarma. “nd” selecciona el relé
normalmente desactivado o normalmente activado “nE”.
rEn : activa el control remoto (mediante conexión en
serie) de la salida 1/2.
!
OR
fig. 23
V
h
PF dmd
WICHTIGE HINWEISE:
• Die gemessene Größe blinkt, wenn ein Alarm aktiviert ist
(siehe Abb. “G” links: VL1, 200V). Es ist möglich mehr
als einen Alarm mit der selben Größe verbinden; wenn
der erste Alarm aktiviert ist, blinkt der Bereich der Größe.
Die “al” (•) LED bedeutet die Aktivierung von einem der
zwei Ausgänge (Relais oder offener Kollektor Ausgang).
• Wenn beide digital Ausgänge im Gerät vorhanden sind
(Relais oder offener Kollektor), ist es möglich bis zu 16
Alarme zu kontrollieren; die 16 Alarme können zu
Ausgang 1 und/oder Ausgang 2 verbunden sein.
• Wenn “var” oder “W negative sind, blinkt der Dezimal punkt Äußerst Rechts, entsprechend der negativen
Größe (siehe Abb. “H” links).
• Sollte negative Energie angezeigt werden, ist zu beachten, dass diese nicht gezählt wird.
■ AJUSTE OUT 1 / OUT2
A.01... A.16.
VA
h
L
3
NOTE IMPORTANTI:
• La variabile misurata lampeggia se si trova in stato di
allarme (vedi figura “G” a sinistra: V L1, 200V). E’ possibile abbinare più allarmi alla stessa variabile, la prima
condizione di allarme che si verificherà determinerà il
lampeggio del campo variabile. La spia “al” (•) indica
l’attivazione di una delle due uscite (relè o a collettore
aperto) nel caso siano selezionate come allarme.
• Qualora lo strumento abbia installato le due uscite digitali
(relè o a collettore aperto) è possibile gestire fino a 16 allarmi che possono essere abbinati all’uscita 1 e/o uscita 2.
• Se “var” o “W” sono negativi il punto decimale all’estrema destra lampeggia in corrispondenza della variabile negativa (vedi figura “H” a sinistra).
• Qualora lo strumento visualizzi una potenza negativa ,
l’energia relativa non verrà in alcun modo conteggiata.
FRANÇAIS
■ RÉGLAGE OUT 1 / OUT2
ou.1 / ou.2 : réglage sorties 1 / 2, sélectionner:
EnE : retransmission de la valeur de l'énergie active
“Act” ou réactive “rEA” par impulsions. “dP” pour
sélectionner le point décimal. “PuL” pour sélectionner
le nombre d’impulsions par kWh/kvarh de 0,01 à 500.
ALr : activation de la sortie d’alarme. “nd” sélection du
relais normalement ouvert ou le relais normalement
fermé “nE”.
rEn : activation du contrôle à distance (par connexion
série) de la sortie 1-2.
AND
fig. 22
V
VA
h
L
3
AND/OR
fig. 21
V
VA
VA
h
L
3
L
1
▲
L
1
L
2
Var
r16 VA L3
r05 V L2-3
h
▲
r
r01 V L1
k
W
L
3
Var
V
VA
L
2
r
▲
L
1
Var
▲
Hz
▲
L
3
■ ALARM SETUP MENU
A.O1 : “oFF” disabilita l’allarme A.01, passando all’allarme successivo (fino a A.16). Le eventuali impostazioni
selezionate precedentemente rimangono memorizzate.
“on” abilita l’allarme, quindi selezionare la variabile da
controllare:
VAr : scegliere la variabile da controllare (vedi tabella “I”).
no, per passare direttamente alle impostazioni dell’allarme successivo
YES, per continuare la programmazione di tutti i
parametri relativa all’allarme in questione:
d.P.o : disattivazione dell’allarme all’accensione, “no”
per disattivare la funzione o “YES” per attivarla.
tYP : seleziona il tipo di allarme: in salita (uP) o in
discesa (do) a finestra interno (in) a finestra
esterno (out).
dP : seleziona la posizione del punto decimale.
Lo.S : seleziona il valore della soglia inferiore.
Hi.S : seleziona il valore della soglia superiore.
dEL : seleziona il tempo di ritardo all’attivazione da 0
a 255 secondi.
Fun : seleziona la funzione di OR o di AND
(vedere riquadro in basso“AND/OR”).
out : seleziona il relè da attivare in caso di allarme
“rl.1” uscita relè 1 o “rl.2” uscita relè 2.
▲
S
ESPAÑOL
DEUTSCH
■ EINSTELLUNG OUT 1 / OUT2
ou.1 / ou.2 : Einstellung Ausgang 1 / 2, wählen:
EnE : nochmalige Übertragung des Wertes der
Wirkenergie “Act” oder der Blindenergie “rEA” über
Impulse. “dP” Wahl des Dezimalpunkts “PuL” Wahl der
Anzahl von Impulse bei kWh/kvarh von 0,01 bis 500.
ALr : Alarm-Ausgang Aktivierung. “nd” Wahl des
Relaisstatus: normal unerregt oder normal erregt
“nE”. rEn : Aktivierung des Fernkontrolle (über serielle Schnittstelle) des 1 / 2 Ausgang.
■ EINSTELLUNG ALARM MENU
A.O1 : “oFF” Deaktivierung des Alarms A.01, und weiter
zu den nächsten (bis zu A 16). Alle andere Einstellungen
bleiben gespeichert. “on” Aktivierung des Alarms und
Wahl der zukontrollierenden Größe:
VAr: Wahl der zu kontrollierenden Größe (siehe Tab. “ I”).
no, direkt zur Einstellung des nächsten Alarmes gehen
YES, alle weiteren Parameter des eingestellten
Alarmes programmieren.
d.P.o : Desaktivierung des Alarms bei Einschaltung, “no”
um diese Funktion zu deaktivieren oder “YES” um die
Funktion zu Aktivieren.
tYP : Wahl des Typs des Alarms: Höchstwert des
Alarms (uP) oder Mindestwert des Alarms (do), int.
Fensteralarm (in), ext. Fensteralarm (out).
dP : Wahl der Position des Dezimalpunkts.
Lo.S : Wahl der Mindestschwellengrenze
Hi.S : Wahl der Hochstschwellengrenze
dEL : Wahl Alarm-Einschaltverzögerung von 0 bis 255 Sek.
Fun: Wahl der OR oder AND Funktion (siehe die
“OR/AND” Abbildung hier unten) .
out : Wahl ob Relais normal unerregt. “rl.1”
Relaisausgang 1 oder “rl.2” Relaisausgang 2.
L
2
▲
S
S
S
ITALIANO
■ SETUP OUT 1 / OUT2
ou.1 / ou.2 : setup uscita 1 / 2, selezionare:
EnE : ritrasmette il valore dell’energia attiva “Act” o
reattiva “rEA” mediante impulsi. “dP” seleziona il
punto decimale. “PuL” seleziona il numero di impulsi
per kWh/kvarh che si desidera generare da 0,01 a 500.
ALr : attiva l’uscita allarme. “nd” seleziona il relè normalmente diseccitato o normalmente eccitato “nE”.
rEn : attiva il controllo remoto (mediante connessione
seriale) dell’uscita 1/2.
▲
W
h
L
3
var
Hz
fig. 27
V
k
A
M
L
1
VA
L
2
▲
S
■ SETUP OUT 1 / OUT2
ou.1 / ou.2 : setup of output 1 / 2, select:
EnE : retransmits the value of the active energy “Act”
or the reactive one “rEA” by means of pulses. “dP”
selects the decimal point. “PuL” selects the number
of pulses per kWh/kvarh from 0,01 to 500.
ALr : enables the alarm output. “nd” selects the normally disabled relay or the normally enabled one
“nE”.
rEn : activates the remote control (by means of serial
connection) of the 1 / 2 output.
al
PF dmd
kvarh: 556.5 partial meter
▲
W
h
L
3
var
Hz
fig. 28
V
k
A
M
L
1
VA
L
2
▲
S
ENGLISH
c
ALARM SETUP MENU
al
PF dmd
kWh: 6 574.8 partial meter
▲
W
h
L
3
var
Hz
V
k
A
M
VA
L
2
▲
ab
SETUP OUT 2
al
PF dmd
kvar: 3 553 944.9 total m.
▲
W
▲
SETUP OUT 1
h
L
3
var
Hz
al
PF dmd
kWh: 15 933 453.7 total m.
1
Carlo Gavazzi Controls SpA,
Via Safforze, 8 - 32100
Belluno (Italy)
Tel. +39 0437 931000,
Fax +39 0437 931021
CARLO GAVAZZI
A u t o m a t i o n
C o m p o n e n t s
WM14DIN/96 A IM ML 261009 Cod. 8020697
WM14DIN A/WM1496 A
Three Phase power analyser
ENGLISH
■ SAFETY PRECAUTIONS
Read carefully the instruction manual. If the instrument is used in a manner not specified by the producer, the protection provided by the instrument may be
impaired.
Maintenance: make sure that the connections are correctly carried out in order to avoid any malfunctioning or damage to the
instrument. To keep the instrument clean, use a slightly damp
cloth; do not use any abrasives or solvents. We recommend to
disconnect the instrument before cleaning it.
!
■ TECHNICAL SPECIFICATIONS
Rated inputs System type: 3 Current (Shunts), Voltage 4.
Accuracy (@25°C ±5°C, R.H. ≤60%) (display, RS485) with CT=1 and
VT=1; AV5: 1150W-VA-var, FS:230VLN, 400VLL; AV6: 285W-VA-var,
FS:57VLN, 100VLL. Current 0.25 to 6A: ±(0.5% FS +1DGT).
From 0.03A to 0.25A: ±(0.5% F.S.+7DGT). Neutral current from
0.25 to 6A: ±(1.5% FS +1DGT) from 0.09A to 0.25A: ±(1.5%
F.S.+7DGT). Phase-phase voltage ±(1.5% FS +1 DGT). Phase-neutral voltage ±(0.5% FS + 1 DGT). Active and Apparent power, from
0.25 to 6A: ±(1% FS +1DGT); from 0.03A to 0.25A: ±(1% FS
+5DGT). Reactive power from 0.25 to 6A: ±(2% FS +1DGT); from
0.03A to 0.25A: ±(2% FS +5DGT). Active energy Class 1 (Start up
current: 30mA). Reactive energy Class 2 (Start up current: 30mA).
Frequency ±0.1Hz (48 to 62Hz). Harmonic distortion ±3% F.S. (up
to 15th harmonic) (F.S.: 100%).
Additional errors: Humidity≤0.3% FS, 60% to 90% RH.
Temperature drift: 200ppm/°C.
Sampling rate: 1600 samples/s @ 50Hz, 1900 samples/s @ 60Hz.
Display refresh time: 200ms (FFT off) 500ms (FFT on).
Display: Type LED, digit height 14mm (96x96) or 9mm (DIN).
Read-out for instant. var. 3x3 DGT Read-out for energies 3+3+3
DGT (Max indication: 999 999 99.9) Read-out for hour counter
1+3+3 DGT (Max. indication: h 9 999 9.99).
Measurements: Current, voltage, power, power factor, frequency
Type TRMS measurement of distorted waves. Coupling type Direct
Crest factor < 3, max 10A peak.
Input impedance: 380/660VL-L (AV5) 1.6 MΩ ±5%; 120/208VL-L
(AV6) 1.6 MΩ ±5%; Current ≤ 0.02Ω
Frequency: 48 to 62 Hz.
Overload protection: (max values) Continuos voltage/current AV5:
460VLN/800VLL/6A; AV6: 145VLN/250VLL/6A. For 500ms: voltage/current AV5: 800VLN/1380VLL/36A; AV6: 240VLN/416VLL/36A.
Pulse outputs: Number of outputs: up to 2. Programmable from
0.01 to 500 pulses per kWh/kvarh. Pulse duration ≥ 100ms
<120msec (ON), ≥ 120msec (OFF) according to EN62053-31
Relay outputs: Number of outputs: up to 2, independent. Alarm
modes: up alarm, down alarm, in window alarm, out window
alarm, for all the mentioned models there is the function “start-up
deactivation” available. All alarms can be connected to any one of
the available variables (see the table “I”). Set-point adjustment
from 0 to 100% of the displayed scale. Hysteresis: from 0 to full
scale. On-time delay: 0 to 255s. Output status selectable: normally de-energized and normally energized. Min. response time
≤400ms, filters excluded with FFT off; 1s with FFT on and set-point
on-time delay: “0 s”.
Note: the 2 digital outputs can also work as one pulse output and
one alarm output the 2 outputs can also be controlled through a
remote control (RS485).
Static outputs: Purpose for pulse outputs or for alarm outputs
Signal VON 1.2 VDC/ max. 100 mA, VOFF 30 VDC max. Insulation
by means of optocuplers, 4000 VRMS output to measuring inputs,
4000 VRMS output to power supply input.
Relay outputs: Usage for alarm outputs or for pulse outputs.
Relay type: SPST type AC 1-5A @ 250VAC; DC 12-5A @ 24VDC
AC 15-1.5A @ 250VAC; DC 13-1.5A @ 24VDC. Mechanical life:
≥30x106 operations; Elctrical life: ≥105 operations (@ 5A, 250V,
PF1). Insulation 4000VRMS output to measuring input, 4000 VRMS
output to supply input.
RS422/RS485 port: (on request) Multidrop bidirectional (static and
dynamic variables).
Connections: 2 or 4 wires, max. distance 1200m, termination
directly on the instrument. Addresses from 1 to 255, key-pad
selectable. Protocol MODBUS/JBUS (RTU). Data (bidirectional).
Dynamic (reading only): system and phase variables. Static (writing only): all the configuration parameters. Data format: 1 start bit,
8 data bit, no parity,1 stop bit. Baud-rate 4800, 9600,19200,
38400bits/s. Insulation by means of optocouplers, 4000 VRMS
output to measuring input 4000 VRMS output to supply input
Auxiliary power supply: 90 to 260VAC/DC; 16 to 60VAC/DC.
Power consumption: AC: 6 VA DC: 3.5W.
Operating temperature: 0° to +50°C (32° to 122°F). (RH < 90%
non condensing). Storage temperature: -10° to +60°C (14° to
140°F) (RH < 90% non condensing).
Relative humidity (non condensing): <90%. Overvoltage: category Cat. III (IEC 60664, EN60664).
Insulation: (for 1 minute) 4kVACRMS between measuring inputs
and power supply. 4kVAC/DC @ I≤ 3mA between measuring
inputs and RS485/RS232. 4kVAC RMS between power supply
and RS485/RS232.
Dielectric strength: 4kVACRMS (for 1 min).
EMC: emissions, EN61000-6-3 residential environment, commerce
and light industry Immunity, EN61000-6-2 industrial environment.
Pulse voltage (1.2/50µs): EN61000-4-5.
Safety standards: IEC60664, IEC61010-1EN60664, EN61010-1
Approvals: CE. Connections: 5(6) A screw-type Max cable cross
sect. area 2.5 mm2 . Min/Max screws tightening torque:
0.4Nm/0.8Nm.
Housing Dimensions: (WxHxD) 96 x 96 x 63 mm (panel version),
IN / OUT Instruction Sheet
Instrument Features
107.5x90x64.5 (DIN version) . Material ABS self-extinguishing:
UL 94 V-0. Mounting: Panel (96), DIN-rail (DIN). Protection
degree: front IP40 (DIN version), IP65 (96 version). Terminal
blocks: IP20 (96 and DIN version). Weight: approx. 400 g (packing included). Additional technical features: environmental conditions: indoor use only, pollution degree 2, altitude up to 2000m.
■ SOFTWARE FUNCTIONS
Password Numeric code of max. 3 digits; 2 protection levels of
the programming data. 1st level: password “0”, no protection.
2nd level: password from 1 to 999, all data are protected
System selection 3P = balanced 3-phase (1CT, 3 or 4 wires);
3P.n = unbalanced 3-phase with or without neutral (3 or 4 wires);
3P.I = balanced 3-phase (1CT, 2 wires); 3P.A = unbalaced 3-phase
ARON connection (3 wires); 2P = 2-phase (3 wires); 1P = single
phase (2 wires).
Transformer ratio. CT 1 to 60000. VT/PT 1.0 to 6000.0
Filter. Operating range 0 to 100% of the displayed scale. Filtering
coefficient 1 to 32. Filter action Measurements, alarms, serial output
(fundamental variables: V, A, W and their derived ones).
Displaying Up to 3 variables per page.
Alarms working mode “OR” or “AND” or “OR+AND” functions
(see OR/AND table). Freely programmable on up to 16 alarms. The
alarms can be connected to any variables available in the “ I “ table.
Reset. By means of keypad: all variables including instantaneous,
min, max, dmd and counters variables. Max: A1, A2, A3, W1, W2,
W3, Wdmd1-2-3, Wsys dmd, VAsys dmd; min: PF1, PF2, PF3; A1,
A2, A3; V1, V2, V3; - dmd: A1, A2, A3, VA1, VA2, VA3, VAsys, W1,
W2, W3, Wsys, A.
All counters: total energies: kWh, kvarh; - partial energies: kWh,
kvarh; - hour counter. Max and min.
ITALIANO
■ NORME DI SICUREZZA
Leggere attentamente il manuale istruzioni. Qualora l’apparecchio venisse adoperato in un modo non specificato dal
costruttore, la protezione prevista dall’apparecchio
potrebbe essere compromessa. Manutenzione: assicurarsi che i collegamenti siano effettuati correttamente al
fine di evitare qualsiasi malfunzionamento o danneggiamento
dello strumento. Per mantenere pulito lo strumento usare un
panno leggermente inumidito; non usare abrasivi o solventi. Si
consiglia di scollegare lo strumento prima di pulirlo.
!
■ CARATTERISTICHE TECNICHE
Tipo di sistema ingressi nominali: 3 corrente (shunts), 4 tensione.
Precisione: (@25°C ±5°C, R.H. ≤60%) (display, RS485) con TA =1 e
TV=1; AV5: 1150W-VA-var, FS:230VLN, 400VLL; AV6: 285W-VA-var,
FS:57VLN, 100VLL. Corrente: da 0.25 a 6A: ±(0.5% FS +1 DGT),
da 0.03A a 0.25A: ±(0.5%F.S.+7DGT). Corrente di neutro da 0.25
a 6A: ±(1.5% FS +1DGT), da 0.09A a 0.25A: ±(1.5%FS+7DGT).
Tensione concatenata: ±(1.5% FS +1 DGT). Tensione stellata:
±(0.5% FS + 1 DGT). Potenza attiva e apparente, da 0.25 a 6A:
±(1% FS +1DGT), da 0.03A a 0.25A: ±(1% FS +5DGT). Potenza
reattiva da 0.25 a 6A: ±(2% FS +1DGT), da 0.03A a 0.25A: ±(2%
FS +5DGT). Energia attiva classe 1 (corrente di avviamento:
30mA). Energia reattiva classe 2 (corrente di avviamento: 30mA).
Frequenza ±0.1Hz (48 a 62Hz). Distorsione armonica ±3% F.S.
(fino alla 15a armonica) (F.S.: 100%).
Errori addizionali: Umidità: ≤0.3% FS, 60% a 90% U.R.
Deriva termica: 200ppm/°C.
Campionamento: 1600 campioni/s @ 50Hz, 1900 campioni/s @ 60Hz.
Rinfresco display: 200ms (FFT off) 500ms (FFT on).
Display: tipo a LED, altezza digit 14mm (96x96) o 9mm (DIN).
Visualizzazione var. istantanee 3x3 DGT visualizzazione energie
3+3+3 DGT (Max indicazione: 999 999 99.9) Visualizzazione contaore 1+3+3 DGT (Max. indicazione: h 9 999 9.99).
Misure: corrente, tensione, potenza, fattore di potenza, frequenza,
TRMS di forme d’onda distorte. Accoppiamento: diretto. Fattore di
cresta < 3, max picco 10A .
Impedenza d’ingresso: 380/660VL-L (AV5) 1.6 MΩ ±5%; 120/208VLL (AV6) 1.6 MΩ ±5%; Corrente ≤ 0.02Ω
Frequenza: 48 a 62 Hz.
Protezione dai sovraccarichi: (valori massimi); continuativo: tensione/corrente, AV5: 460VLN/800VLL/6A; AV6: 145VLN/
250VLL/6A. Per 500ms: tensione/corrente AV5: 800VLN/
1380VLL/36A; AV6: 240VLN/416VLL/36A.
Uscite impulsive: Numero di uscite: fino a 2. Programmabile da
0.01 a 500 impulsi per kWh/kvarh. Durata dell’impulso: ≥ 100ms
<120msec (ON), ≥ 120msec (OFF) secondo EN62053-31
Uscite relè: numero di uscite: fino a 2, indipendenti. Tipo allarme:
allarme di massima, allarme di minima, allarme finestra interna,
allarme finestra esterna, per tutti i modelli menzionati è disponibile la funzione “disattivazione all’avviamento”. Tutti gli allarmi possono essere associati ad una qualsiasi delle variabili disponibili
(vedi tabella “ I ”). Regolazione del set-point da 0 a 100% della
scala visualizzata. Isteresi: da 0 al fondo scala. Ritardo all’attivazione: 0 a 255s. Stato dell’uscita: selezionabile: normalmente diseccitato e normalmente eccitato. Tempo min. di risposta: ≤400ms,
filtri esclusi con FFT off; 1s con FFT on e ritardo attivazione soglia:
“0 s”.
Nota: le due uscite digitali possono anche lavorare come un’uscita
impulsi e un’uscita allarmi. Le due uscite possono essere controllate tramite un controllo remoto (RS485).
Uscite statiche: tipo di utilizzo: per uscite impulsi o uscite allarmi.
Segnale VON 1.2 VCC/ max. 100 mA, VOFF 30 VCC max.
Isolamento per mezzo di optoisolatori, uscita 4000 VRMS verso
ingressi di misura, uscita 4000 VRMS verso ingresso alimentazione.
Uscite relè: utilizzo per uscite di allarme o per uscite impulsi.
Tipo di relè: tipo SPST AC 1-5A @ 250VCA; DC 12-5A @ 24VCC
AC 15-1.5A @ 250VCA; DC 13-1.5A @ 24VCC. Vita meccanica:
≥30x106 commutazioni: vita elettrica: ≥105 commutazioni (@ 5A,
250V, cosϕ1)Isolamento 4000 VRMS uscita verso ingresso di misura, 4000 VRMS uscita verso ingresso di alimentazione.
Porta RS422/RS485: (a richiesta) Multidrop bidirezionale (variabili
statiche e dinamiche).
Collegamenti: 2 o 4 fili, max. distanza 1200m, terminazione direttamente sullo strumento. Indirizzi da 1 a 255, selezionabile da
tastiera. Protocollo MODBUS/JBUS (RTU). Dati (bidirezionale).
Dinamico (solo lettura): variabili di sistema e di fase. Statico: (solo
scrittura): tutti i parametri di configurazione. Formato dati: 1 bit di
start, 8 bit di dati, nessuna parità,1 bit di stop. Baud-rate 4800,
9600,19200, 38400bits/s. Isolamento per mezzo di optoisolatori,
4000 VRMS uscita verso ingresso di misura 4000 VRMS uscita
verso ingresso di alimentazione.
Alimentazione ausiliaria: da 90 a 260VCA/CC; da 16 a 60VCA/CC..
Consumo energia: AC: 6 VA CC: 3.5W.
Temperatura di funzionamento: da 0° a +50°C (da 32° a 122°F).
(UR < 90% senza condensa). Temperatura di immagazzinaggio:
-da -10° a +60°C (da 14° a 140°F) (UR < 90% senza condensa).
Sovratensione: categoria Cat. III (IEC 60664, EN60664).
Isolamento: (per 1 minuto) 4kVCARMS tra ingressi di misura e
alimentazione. 4kVCA/CC @ I≤ 3mA tra ingressi di misura e
RS485/RS232. 4kVCA RMS tra alimentazione e RS485/RS232.
Rigidità dielettrica: 4kVCARMS (per 1 min).
EMC: emissioni, EN61000-6-3 ambiente residenziale, commercio
ed industria leggera; Immunità ambiente industriale EN61000-6-2.
Tensione a impulsi (1.2/50µs): EN61000-4-5.
Norme di sicurezza: IEC60664, IEC61010-1EN60664, EN61010-1
Approvazioni: CE. Collegamenti: 5(6) A a vite; Sezione max. cavo:
2.5 mm2 . Coppia min/max serraggio viti: 0,4Nm/0,8Nm.
Custodia: Dimensioni (LxHxP) 96 x 96 x 63 mm (versione pannello), 107.5x90x64,5 (versione DIN). Materiale ABS autoestinguente: UL 94 V-0. Montaggio: pannello (96), guida DIN. Grado di
protezione: frontale IP40 (versione DIN), IP65 (versione 96).
Morsettiere: IP20 (versione 96 e DIN). Peso: circa 400 g (imballo incluso).
■ FUNZIONI SOFTWARE
Password Codice numerico di max. 3 digits; 2 livelli di protezione
dei dati di programmazione: 1° livello: password “0” , nessuna protezione; 2° livello: password da 1 a 999, tutti i dati sono protetti.
Selezione sistema 3P = bilanciato trifase (1 TA, 3 o 4 fili);
3P.n = sbilanciato trifase con o senza neutro (3 o 4 fili); 3P.I =
bilanciato trifase (1 TA, 2 fili); 3P.A = sbilanciato trifase collegamento ARON (3 fili); 2P = bifase (3 fili); 1P = singola fase (2 fili).
Rapporto di trasformazione TA da 1 a 60000. TV da 1.0 a 6000.0
Filtro. Campo di funzionamento da 0 a 100% della scala visualizzata. Coefficiente di filtro da 1 a 32. Azione del filtro: Misure, allarmi,
uscita seriale (variabili fondamentali: V, A, W e loro derivate).
Visualizzazione fino a 3 variabili per pagina.
Modo di funzionamento degli allarmi “OR” o “AND” o funzioni
“OR+AND” (vedere tabella AND/OR). Liberamente programmabile
fino a 16 allarmi. Gli allarmi possono essere associati a qualsiasi
variabile disponibile nella tabella “ I “.
Reset. Da tastiera: - tutte le variabili incluse le variabili istantanee,
min, max. dmd e contatori. Max: A1, A2, A3, W1, W2, W3,
Wdmd1-2-3, Wsys dmd, VAsys dmd; min: PF1, PF2, PF3; A1, A2,
A3; V1, V2, V3; - dmd: A1, A2, A3, VA1, VA2, VA3, VAsys, W1, W2,
W3, Wsys, A.
Tutti i contatori: Energie totali: kWh, kvarh; - energie parziali: kWh,
kvarh; - contaore - Max. e min.
DEUTSCH
■ SICHERHEITSBESTIMMUNGEN
Bitte lesen Sie sorgfälltig die Bedienungsanleitung. Bei von den
Angaben des Herstellers abweichendem Gebrauch des Gerätes
könnte der Schutz, mit dem das Gerät ausgestattet ist, beschädigt
werden. Wartung: Sicherstellen, daß die Verbindungen korrekt
sind, um falsche Arbeitsweise oder Beschädigung des
Instruments zu vermeiden. Reinigen Sie das Gehäuse in
regelmäßigen Zeitabständen mit einem Tuch und
Reinigungsmittel. Verwenden Sie keine Kratzenden
Reinigungsmittel oder Lösungsmittel. Schalten Sie das Gerät aus,
bevor der Reinigung.
!
■ TECHNISCHE DATEN
Nenneingänge Systemtyp: 3 Strom (Shunts), Spannung 4.
Genauigkeit (@25°C ±5°C, R.L. ≤60%) (Anzeige, RS485) mit St.W.=1
und Sp.W.=1; AV5: 1150W-VA-var, BE:230VLN, 400VLL; AV6: 285W-VAvar, FS:57VLN, 100VLL. Strom 0.25 bis 6A: ±(0.5% BE +1 stellig).
Von 0.03A bis 0.25A: ±(0.5% BE+7 stellig). Nulleiter Strom von
0.25 bis 6A: ±(1.5% BE +1 stellig), von 0.09A bis 0.25A: ±(1.5%
BE+7 stellig). Phase-phase Spannung ±(1.5% BE +1 stellig). PhasenNeutral Spannung ±(0.5% BE + 1 stellig). Wirkleistung und
Scheinleistung, von 0.25 bis 6A: ±(1% BE +1 stellig); von 0.03A bis
0.25A: ±(1% BE +5 stellig). Blindleistung von 0.25 bis 6A: ±(2% BE
+1 stellig); von 0.03A bis 0.25A: ±(2% BE +5 stellig). Wirkenergie
Klasse 1 (Startstrom: 30mA). Blindenergie Klasse 2 (Startstrom:
30mA). Frequenz: ±0.1Hz (48 bis 62Hz). Harmonische Verzerrung
±3% BE (bis zu 15te Harmonische) (BE.: 100%).
Zusätliche Fehler: Feuchtigkeit ≤0.3% BE, 60% bis 90% rL..
Temperaturabweichung: 200ppm/°C.
Abtastrate: 1600 Abtastungen/s @ 50Hz, 1900 Abtastungen/s @ 60Hz.
Anzeigenerneuerungszeit: 200ms (FFT off) 500ms (FFT on).
Anzeige: Typ LED, Segmente:14mm hoch (96x96) oder 9mm
(DIN). Anzeige für Momentanwerte 3x3 DGT Anzeige für Energie
3+3+3 stellig (Max Anzeige: 999 999 99.9) Anzeige für
Stundenzähler 1+3+3 stellig (Max .Anzeige: h 9 999 9.99).
Messungen: Strom, Spannung, Leistung, Leistungsfaktor, Frequenz
TRMS Messung von verzerrten Wellen. Kopplungsart Direkt Crestfaktor < 3, max 10A Spitze.
Eingangsimpedanz: 380/660VL-L (AV5) 1.6 MΩ ±5%; 120/208VL-L
(AV6) 1.6 MΩ ±5%; Strom ≤ 0.02Ω
Frequenz: 48 bis 62 Hz.
Überlastschutz: (Max. Werte) fortwährend Spannung/Strom AV5:
460VLN/800VLL/6A; AV6: 145VLN/250VLL/6A.
Für 500ms: Spannung/Strom AV5: 800VLN/1380VLL/36A; AV6:
240VLN/416VLL/36A.
Impulsausgangs: Anzahl der Ausgänge: bis zu 2. Programmierbar
von 0.01 bis 500 Impulse pro kWh/kvarh. Impulsdauer ≥ 100ms
<120msec (ON), ≥ 120msec (OFF) nach EN62053-31
Relaisausgangs: Anzahl der Ausgänge: bis 2, unabhängig. Alarm
Betriebsarten: Aufwärtsalarm, Abwärtsalarm, int. Fenster-Alarm,
ext. Fenster Alarm, für alle diese Betriebsarten ist die Funktion
“Start-up Deaktivierung” verfügbar. Alle die Alarme können verbunden mit allen verfügbaren Größen sein (siehe Tabelle “I”).
Sollwert-einstellung von 0 bis 100% der angezeigte Skala.
Hysteresis: von 0 bis volle Grösse. On-time Verzögerung: 0 bis
255 s. Ausgangsstatus wählbar; normal unerregt und normal
erregt. Min. Ansprechszeit ≤400ms, ohne Filter, FFT off; 1 s FFT on.
Verzögerung On-time Sollwert: “0 s”
Zu beachten: Die 2 Digitalausgänge können auch als 1 ImpulsAusgang und 1 Alarm-Ausgang funktionieren. Die 2 Ausgänge können auch durch ein Fernsteurung kontrolliert werden (RS485).
Statische Ausgänge: Zweck: für Impulsausgänge oder für
Alarmausgänge. Signal VON 1.2VDC/max.100 mA, VOFF 30VDC max.
Isolation durch Optokoppler 4000 VRMS Ausgang zu Messeingängen,
4000 VRMS Ausgang zu Stromversorgungseingang.
Relaisausgänge: Zweck
für Alarmausgänge oder für
Impulsausgänge.
Relaistyp: SPST AC 1-5A @ 250VAC; DC 12-5A @ 24VDC AC 151.5A @ 250VAC; DC 13-1.5A @ 24VDC.
Mechanische
Lebensdauer: ≥30x106 Schaltspiele; elektrische Lebensdauer:
≥105 Schaltspiele (@ 5A, 250V, PF1). Isolation: 4000VRMS
Ausgang zu Messeingang, 4000VRMS Ausgang zu Strom-versorgungseingang.
RS422/RS485: (auf Anfrage) Multidrop bidirektional (statische und
dynamische Variablen).
Anschlüsse: 2 oder 4 Leiter, max. Länge 1200m, Anschluss direkt
am Gerät. Adressen: von 1 bis 255, über Tastatur wählbar.
Protokoll: MODBUS/JBUS (RTU). Daten (bidirektional).
Dynamisch (nur lesen): System und Phasenvariablen. Statisch
(nur Schreiben): Alle Konfigurationsparameter. Datenformat: 1
Start bit, 8 Datenbit, keine Parit,1 Stopbit. Baud-Rate 4800,
9600,19200, 38400 bits/s. Isolation durch Optokoppler, 4000
VRMS Ausgang zu Messeingang. 4000 VRMS Ausgang zu
Stromversorgung.
Hilfstromversorgung: 90 bis 260VAC/DC; 16 bis 60VAC/DC.
Stromverbrauch: AC: 6 VA DC: 3.5W.
Betriebstemperatur: 0° bis +50°C (32° bis 122°F). (rL. < 90%
nicht kondensierend). Lagertemperatur: -10° bis +60°C (14° bis
140°F) (rL < 90% nicht kondensierend).
Überspannungs-Kategorie: Kat. III (IEC 60664, EN60664).
Isolation: (1 Minute) 4kVAC RMS zwischen Messeingängen und
Stromversorgung. 4kVAC/DC @ I≤ 3mA zwischen Messeingängen
und RS485/RS232. 4kVAC RMS zwischen Stromversorgung und
RS485/RS232.
Dielektrische Stärke: 4kVACRMS (1 Min).
EMC: Emissionen, EN61000-6-3 Wohnungumgebung, Handel und
Leichtindustrie, Immunität EN61000-6-2 Industrieumgebung.
Impulsspannung (1.2/50µs): EN61000-4-5.
Sicherheitsnormen: IEC60664, IEC61010-1EN60664, EN61010-1
Genehmigungen: CE. Anschlüsse: 5(6) A Schraubbefestigung Max
Kabelquerschnittfläche 2.5 mm2. Anzugsmoment: 0.4Nm/0.8Nm.
Gehäuse: (WxHxD) 96 x 96 x 63 mm (Tafel Montage),
107.5x90x64.5 (DIN-Schiene) . Material ABS selbstlöschend: UL
94 V-0. Montage: Tafel (96), DIN-schiene (DIN). Schutzart: Front
IP40 (DIN-schiene), IP65 (96 Typ). Klemme: IP20 (96 und DIN).
Gewicht: ungefähr 400 g (einschl. Verp.)
■ SOFTWAREFUNKTIONEN
Passwort Zahlenkode mit maximal 3 Stellen; 2 Schutzebenen für
die Progammdaten: 1 Ebene: Passwort “0”, kein Schutz. 2te
Ebene; Passwort von 1 bis 999, alle Daten werden geschützt.
Systemartwahl 3P = symmetriche Last 3-Phasig (1St.W., 3 oder 4
Leiter); 3P.n = unsymmetriche Last 3-Phasig mit oder ohne Nulleiter
(3 oder 4 Leiter); 3P.I = symmetriche Last 3-Phasig (1St.W., 2 Leiter);
3P.A = unsymmetriche Last 3-Phasig ARON Anschluss (3 Leiter); 2P
= 2-Phasig (3 Leiter); 1P = 1 Phasig (2 Leiter).
Wandlersverhältnis. St.W.1 bis 60000. Sp.W. 1.0 bis 6000.0
Filter. Funktionsbereich 0 bis 100% der angezeigte Skala.
Filterkoeffizient 1 bis 32. Filterwirkung: Messungen, Alarme, serieller
Ausgang (Grundvariablen: V, A, W und ihre Ableitungen).
Anzeige Bis zu 3 Größe bei jeder Seite.
Alarme Funktionsart “OR” oder “AND” oder “OR+AND”
Funktionen (siehe “AND/OR” Tabelle). Frei programmierbar auf bis
zu 16 Alarme. Die Alarme können mit allen in der Tabelle “ I “
anschliessbaren Variablen angeführten werden.
Rücksetzen. Mittels Tastatur:
Alle Variablen einschließlich momentane, min., max., dmd, und
Zählervariablen.
Max: A1, A2, A3, W1, W2, W3, Wdmd1-2-3, Wsys dmd, VAsys
dmd; min: PF1, PF2, PF3; A1, A2, A3; V1, V2, V3; - dmd: A1, A2,
A3, VA1, VA2, VA3, VAsys, W1, W2, W3, Wsys, A.
Alle Zähler. Gesamtenergien: kWh, kvarh; - Teilenergien: kWh,
kvarh; - Stundenzähler. Max. und Min.
FRANÇAIS
■ NORMES DE SECURITE’
Lisez le mode d’emploi et respectez scrupuleusement les
instructions. Si on utilise l’instrument autrement que de la manière indiquée par le producteur, on peut endommager les protections
dont l’instrument est doté.
Maintenance: s’assurer que les câblages sont bien connectés
pour eviter tout malfonctionnement ou dommage de
l’appareil. Nettoyer périodiquement l’étui avec un linge
une peu humide; ne pas utiliser d’abrasifs, ni de solvants. Déconnecter l’appareil avant de le nettoyer.
!
■ CARACTERISTIQUES D’ENTREE
Type système entrées nominales: 3 courant (Shunts), Tension 4.
Précision (@25°C ±5°C, H.R. ≤60%) (Affichage, RS485) avec TC=1 et
TT=1; AV5: 1150W-VA-var, FS:230VLN, 400VLL; AV6: 285W-VA-var,
FS:57VLN, 100VLL. Courant 0.25 à 6A: ±(0.5% PE +1DGT).
De 0.03A à 0.25A: ±(0.5% PE+7 DGT). Courant de neutre 0.25 à
6A: ±(1.5% PE +1DGT), de 0.09A à 0.25A: ±(1.5% PE+7 DGT).
Tension phase-phase ±(1.5% PE +1 DGT). Tension phase-neutre
±(0.5% PE + 1 DGT). Puissance active et apparent, de 0.25 à 6A:
±(1% PE +1 DGT); de 0.03A à 0.25A: ±(1% PE +5DGT). Puissance
réactive 0.25 à 6A: ±(2%PE +1DGT); de 0.03A à 0.25A: ±(2% PE
+5DGT). Energie active, classe 1 (Courant de démarrage: 30mA).
Energie réactive, classe 2 (Courant de démarrage: 30mA).
Fréquence ±0.1Hz (48 à 62Hz). Distorsion harmonique ±3% PE
(jusqu’à la 15ème harmonique) (PE: 100%).
Erreurs additionnelles: Humidité≤0.3% PE, 60% à 90% HR
Dérive de température: 200ppm/°C.
Taux d’échantillonnage: 1600 échantillonnages/s @ 50Hz, 1900
échantillonnages/s @ 60Hz.
Temps de refraîchissement: 200ms (FFT off) 500ms (FFT on).
Afficheur: Type LED, hauteur chiffres 14mm (96x96) ou 9mm
(DIN). Lecture des var. instantanées. 3x3 DGT Lecture des énergies 3+3+3 DGT (Indicat. max.: 999 999 99.9) Lecture compteur
d’heures 1+3+3 DGT (Max. indication: h 9 999 9.99).
Mesures: courant, tension, puissance, facteur de puissance, fréquence. Méthode de mesure: Mesure de valeur efficace vraie de formes d’ondes distordues. Type de couplage: direct. Facteur de crête.
< 3, max 10A crête.
Impédance d’entrée: 380/660VL-L (AV5) 1.6 MΩ ±5%; 120/208VL-L
(AV6) 1.6 MΩ ±5%; Courant ≤ 0.02Ω
Fréquence: 48 à 62 Hz.
Protection contre les surcharges: (valeur max.) Tension/courant
continu AV5: 460VLN/800VLL/6A; AV6: 145VLN/250VLL/6A.
Pour 500ms: tension/courant AV5: 800VLN/1380VLL/36A; AV6:
240VLN/416VLL/36A.
Sorties impulsions: Nombre de sorties: jusqu’à 2. Programmable
de 0.01 à 500 impulsions pour kWh/kvarh. Durée d’impulsions ≥100ms
<120msec (ON), ≥120msec (OFF) suivant EN62053-31.
Sorties relais: Nombre de sorties: jusqu’à 2, indépendantes.
Modes d’alarme: alarme haute, alarme basse, alarme basse avec
désactivation au démarrage, alarme dans fenêtre, alarme fenêtre
extérieure, pour tous ces modes d’alarme, la fonction “désactivation au démarrage est disponible. Tous les alarmes peuvent être
connectés à n’importe quel variable disponible (voir la table “I”).
Régulation du point de consigne de 0 à 100% de l’échelle affichée.
Hystérésis: de 0 à pleine d’échelle. Temporisation activée: de 0 à
255 s. Etat sortie: sélectionnable; normalement déactivé, normalement activé. Temps de réponse min.: ≤400ms, filtres exclus
avec FFT off; 1 s avec FFT on et point de consigne sur temporisation activée: “0 s”.
Remarque: les 2 sorties numériques peuvent aussi fonctionner
comme une sortie impulsion et une sortie alarme; Les deux sorties
peuvent être controlées par un contrôle remote (RS485).
Sorties statiques: type d’emploi: pour sortie impulsions ou pour sorties alarme. Signal VON 1.2 VCC/ max. 100 mA, VOFF 30 VCC max.
Isolation au moyen de photocoupleurs; 4000 VRMS de la sortie sur
entrées de mesure, 4000 VRMS de la sortie à l’entrée d’alimentation.
Sorties relais: emploi pour sorties alarmes ou sorties impulsions.
Type de relais: SPST, AC 1-5A @ 250VCA; DC 12-5A @ 24VCC AC
15-1.5A @ 250VCA; DC 13-1.5A @ 24VCC. Vie mécanique:
≥30x106 exécutions; vie électrique: ≥105 exécutions (@ 5A, 250V,
PF1). Isolation au moyen de photocoupleurs, 4000 VRMS de la sortie sur entrée de mesure, 4000VRMS de la sortie à l’entrée alimentation.
RS422/RS485: (sur demande) Multidrop bidirectionnel (variables
statiques et dynamiques).
Connexions: 2 ou 4 fils, distance max. 1200m, terminaison directement sur l’appareil. Addresses: de 1 à 255, selectable par clavier.
Protocole MODBUS/JBUS (RTU). Données (bi-directionnelles).
Dynamique (lecture seulement): variables système et phase.
Statique (écriture seulement). Tous les paramètres de configuration. Format données: 1 bit de départ, 8 bits der données, aucune
parité, 1 bit d’arrêt. Débit baud 4800, 4800, 9600,19200, 38400
bits/s. Isolation: au moyen de photocoupleurs, 4000 VRMS entre
sortie et entrée de mesure; 4000 VRMS entre sortie et entrée alimentation.
Alimentation électrique auxiliaire: 90 à 260VCA/CC; 16 à 60VCA/CC.
Puissance consummée: AC: 6 VA CC: 3.5W .
Température de fonctionnement: 0° à +50°C (32° à 122°F). (HR
< 90% sans condensation). Température de stockage: -10° à +60°C
(14° à 140°F) (HR < 90% sans condensation).
Catégorie surtension: Cat. III (IEC 60664, EN60664).
Isolation: (pendant 1 minute) 4kVCARMS entre entrées de mesure et alimentation. 4kVCA/CC @ I≤ 3mA entre entrées de mesure et
RS485/RS232. 4kVCA RMS entre alimentation et RS485/RS232.
Puissance diélectrique: 4kVACRMS (pour 1 min).
EMC: emissions, EN61000-6-3 environnement résidentiel, commerce et industrie légère, EN61000-6-2 environnement industriel.
Tension impulsionnelle (1.2/50µs): EN61000-4-5.
Normes de sécurité: IEC60664, IEC61010-1EN60664, EN61010-1
Conformités: CE. Connexions: 5(6) A type à vis. Zone section trans.
câble max. 2.5 mm2. Min/Max couple de serrage: 0.4Nm/0.8Nm.
Boîtier: (WxHxD) 96 x 96 x 63 mm (version tableau),
107.5x90x64.5 (version DIN). Matériel ABS auto-extinguible: UL
94 V-0. Montage: tableau (96), rail DN (DIN). Degré de protection: front IP40 (version DIN), IP65 (version 96). Borne a vis:
IP20 (version 96 et DIN). Poids: approx. 400 g (emballage inclu).
■ FONCTIONS LOGICIELS
Mot de Passe Code numérique à max. 3 digits; 2 niveaux de protection des données de programmation: Niveau 1: mot de passe
“0”, pas de protection; Niveau 2: mot de passe de 1 à 999, toutes
les données sont protégées.
Sélection du système 3P = équilibré triphasé (1TC, 3 ou 4 fils);
3P.n = non équilibré triphasé avec ou sans neutre (3 ou 4 fils); 3P.I
= équilibré triphasé (1TC, 2 fils); 3P.A = non équilibré triphasé
connexion ARON (3 fils); 2P = biphasé (3 fils); 1P = monophasé
(2 fils).
Rapport transformateur. TC 1 à 60000. TT 1.0 à 6000.0
Filtre. Gamme fonctionnement 0 à 100% de l’échelle affichée.
Coefficient de filtrage 1 à 32. Action filtre: mesures, alarmes, sortie
série (variables fondamentales: V, A, W et leurs dérivées).
Affichage Jusqu’à 3 variables per page.
Mode de fonctionnement alarmes: fonctions “OR” ou “AND” ou
“OR+AND” (voir tableau “AND/OR”).
Programmable librement jusqu’à 16 alarmes. Les alarmes peuvent
être connectées à n’importe quelles variables disponibles dans le
tableau “ I ”.
Réinitialiser. Par clavier: toutes les variables y compris celles
instantanées, min, max, dmd et variables compteurs. Max: A1, A2,
A3, W1, W2, W3, Wdmd1-2-3, Wsys dmd, VAsys dmd; min: PF1,
PF2, PF3; A1, A2, A3; V1, V2, V3; - dmd: A1, A2, A3, VA1, VA2, VA3,
VAsys, W1, W2, W3, Wsys, A.
Tous les compteurs. Energies totales: kWh, kvarh; - énergies par-
tielles: kWh, kvarh; - compteurs horaire. Max et min.
ESPAÑOL
■ NORMAS DE SEGURIDAD
Leer el manual y seguir atentamente las instrucciones. Si se utiliza el equipo de manera distinta de como indica el Fabricante, se
puede dañar la protección de la que está provisto el instrumento.
Mantenimiento: Asegurarse de que las conexiones son correctas
para evitar un mal funcionamiento o daños en el instrumento. Para
tener el instrumento limpio, limpiar periódicamente la carcasa con
un trapo un poco humedecido. No utilizar productos abrasivos o
disolventes. Desconectar el equipo antes de limpiarlo.
!
■ ESPECIFICACIONES TÉCNICAS
Entradas nominal, tipo de sistema: 3 Intensidad
(Shunts), tensión 4.
Précision (@25°C ±5°C, R.H. ≤60%) (display, RS485) con TC=1 y
TT=1; AV5: 1150W-VA-var, FS:230VLN, 400VLL; AV6: 285W-VA-var,
FS:57VLN, 100VLL. Intensidad 0.25 a 6A: ±(0.5% f.e. +1díg).
De 0.03A a 0.25A: ±(0.5% f.e.+7 díg). Intensidad de neutro 0,25 a
6A: ±(1.5% f.e.+1díg) de 0.09A a 0.25A: ±(1.5% f.e.+7díg).
Tension fase-fase ±(1.5% f.e.+1 díg). Tension fase-neutro ± (0.5%
f.e. + 1 díg). Potencia activa y aparente, de 0.25 a 6A: ± (1% f.e.
+1 díg); de 0.03A a 0.25A: ±(1% f.e. +5díg). Potencia reactiva de
0.25 a 6A: ±(2% f.e. +1díg), de 0.03A a 0.25A: ±(2% f.e. +5díg).
Energia activa clase 1 (Intensidad de arranque: 30mA). Energia
reactiva clase 2 (Intensidad de arranque: 30mA). Frecuencia
±0.1Hz (de 48 a 62Hz). Distorsión armónica ±3% f.e. (hasta el
armónico 15°) (f.e.: 100%).
Errores adicionales: humedad ≤0.3% f.e, de 60% a 90% HR.
Deriva térmica: 200ppm/°C.
Frecuencia de muestreo: 1600 lecturas/s @ 50Hz, 1900 lecturas/s @ 60Hz.
Tiempo refresco display: 200ms (FFT off) 500ms (FFT on).
Display: tipo LED, dígito 14mm (96x96) o 9mm (DIN). Lectura
para variables instant. 3x3 DGT Lectura para energías 3+3+3 díg
(Indicación max: 999 999 99.9) Lectura para cuenta horas 1+3+3
DGT (Max. Indicación: h 9 999 9.99).
Medidas: Intensidad, tensión, potencia, factor de potencia, frecuencia. Valor TRMS de tensión/intens. de ondas distorsionadas. Tipo de
conexión: directa. Factor de cresta < 3, Pico max 10A .
Impedancia de entrada: 380/660VL-L (AV5) 1.6 MΩ ±5%;
120/208VL-L (AV6) 1.6 MΩ ±5%; Intensidad:≤ 0.02Ω
Frecuencia: da 48 a 62 Hz.
Sobrecarga: (valores max.) tensión/intensidad permanente: AV5:
460VLN/800VLL/6A; AV6: 145VLN/250VLL/6A.
Durante 500ms: tensión/intensidad AV5: 800VLN/1380VLL/36A;
AV6: 240VLN/416VLL/36A.
Salidas de pulso: Número de salidas: hasta 2. Programables de
0.01 a 500 pulsos por kWh/kvarh. Duración de pulso ≥ 100ms
<120msec (ON), ≥120msec (OFF) según norma EN62053-31.
Salidas de relé: Número de salidas: hasta 2, independiente. Modos
de alarma: alarma de max, alarma de min., alarma dentro de banda,
alarma fuera de banda, para todos estos modos está la función con
inhibición a la conexión. Todas las alarmas pueden ser conectadas
a cualquiera de las variables (ver tabla “ I”). Ajuste punto de consigna de 0 a 100% de la escala visualizada. Histéresis: de 0 a la escala completa. Retardo a la conexión: de 0 a 255s. Estado de salida seleccionable: normalmente desactivada y normalmente activada. Tiempo
min. de respuesta: ≤400ms, filtros excluidos con FFT off; 1s con FFT
on. Retardo conexión alarma: “0 s”.
Nota: las 2 salidas digitales también pueden funcionar como una
salida de pulso y una de alarma. Las 2 salidas pueden también ser
controladas mediante un control remoto (RS485).
Salidas estáticas: Proposito para salidas de alarma o para salidas de
pulso. Señal VON 1.2VCC/ max. 100mA,VOFF 30VDC max. Aislamiento
mediante optoacopladores, 4000VRMS entre salida y entradas de
medida, 4000VRMS entre salida y entrada de alimentación.
Salidas de relé: utilización para salidas de alarma o para salidas
de pulso. Relé tipo SPST AC 1-5A @ 250VCA; DC 12-5A @ 24VCC
AC 15-1.5A @ 250VCA; DC 13-1.5A @ 24VCC. Vida mecánica:
≥30x106 operaciones; Vida eléctrica:: ≥105 operaciones (@ 5A,
250V, PF1). Aislamiento 4000VRMS entre salida y entrada de medida, 4000 VRMS entre salida y entrada de alimentación.
Puerto RS422/RS485: (opcional) Multiterminal bidireccional (variables estáticas y dinámicas). Conexiones: 2 o 4 hilos, max. distancia
1200m, con terminación directa en el instrumento. Dirección: de 1 a
255, seleccionable por teclado. Protocolo MODBUS/JBUS (RTU).
Datos (bidireccionales). Dinámicos (solo lectura): variables del sistema y de fase. Estáticos (solo escritura): todos los parámetros de
configuración Formato de datos: 1 bit de arranque, 8 bits de datos,
sin paridad, 1 bit de parada. Velocidad en baudios: 4800,
9600,19200, 38400bits/s. Aislamiento: mediante optoacopladores,
4000 VRMS entre salida y entrada de medida 4000 VRMS entre salida y entrada de alimentación.
Alimentación auxiliar: 90 a 260VCA/CC; 16 a 60VCA/CC..
Temperatura de funcionamiento: 0° a +50°C (32° a 122°F). (HR
<90% sin condensación). Temperatura de almacenamiento -10° a
+60°C (14° a 140°F) (HR < 90% sin condensación).
Sobretensión: Cat. III (IEC 60664, EN60664).
Aislamiento: (durante 1 minuto) 4kVCARMS entre entradas de
medida y alimentación. 4kVCA/CC @ I ≤ 3mA entre entradas de
medida y RS485/RS232.
4kVCA RMS entre alimentación y RS485/RS232.
Rigidez dielectrica: 4kVCARMS (durante 1 min).
EMC: emisiones, EN61000-6-3 entornos residenciales, comercio
e industria ligera, EN61000-6-2 entornos industriales.
Tensión de pulso (1.2/50µs): EN61000-4-5.
Normas de seguridad: IEC60664, IEC61010-1EN60664,
EN61010-1
Homologación: CE. Conexiones: 5(6) A tornillo.
Sección máx. del cable 2.5 mm2.Par de apriete mín/máx:
0.4Nm/0.8Nm. Dimensiones de la caja: (WxHxD) 96 x 96 x 63
mm (versión panel), 107.5x90x64.5 (versión DIN). Material ABS
autoexitinguible: UL 94 V-0. Montaje: Panel (96), carril DIN (DIN).
Grado de protección: frontal IP40 (versión DIN),
IP65 (versión 96). Bloque de terminales: IP20 (versión 96 y DIN).
Peso: aprox. 400 g (embalaje incl.).
■ FUNCIONES DEL SOFTWARE
Clave: Código numérico de 3 díg.; 2 niveles de protección de los
datos de programación. 1er nivel: clave “0”, sin protección. 2do
nivel: clave de 1 a 999, todos los datos están protegidos.
Selección del sistema 3P = carga equilibrada trifásico (1 CT 3 o
4 hilos); 3P.n = carga desequilibrada trifásico con o sin neutro (3
o 4 hilos); 3P.I = carga equilibrada trifásica (1 CT 2 hilos); 3P.A =
carga desequilibrada trifásico conexión ARON (3 hilos); 2P = bifásico (3 hilos); 1P = monofásico (2 hilos).
Relación del transformador. CT 1 a 60000. VT 1.0 a 6000.0
Filtro. Escala operativa 0 a 100% de la escala visualizada.
Coeficiente de filtrado 1 a 32. Acción de filtrado: medidas, alarmas,
salida serie (variables fundamentales: V, A, W y sus derivadas).
Visualización hasta 3 variables por página.
Modo de funcionamiento de las alarmas: funciones “OR” o
“AND” o “OR+AND” (ver tabla “AND/OR”). Hasta 16 alarmas libremente programables. Las alarmas pueden ser conectadas a cualquier variable de la tabla “ I ”.
Puesta a cero. Por medio del teclado: todas las variables, incluidas variab. instant., min, max, dmd y variables de contadores.
Max: A1, A2, A3, W1, W2, W3, Wdmd1-2-3, Wsys dmd, VAsys
dmd; min: PF1, PF2, PF3; A1, A2, A3; V1, V2, V3; - dmd: A1, A2,
A3, VA1, VA2, VA3, VAsys, W1, W2, W3, Wsys, A.
Todos los contadores. Energías totales: kWh, kvarh; - Energías
totales: kWh, kvarh; - contador horario. Max y min.
[9]
17 19 21 24 23
5 6 7 8 9 1011 12 13 14
3
1
F1
L1
L2
L3
96
(back)
[10]
17 15 24 23
L1
15
17
19
21
23 24 25 26 27 28
L2
L3
N
F1= 315mA
17 15 24 23
[11]
17 15 24 23
[1]
F1
F1
L1
L1
L2
L3
N
N
17 19 15 24 23 26 25
[2]
F1
L1
F
L2
[13]
N
ITALIANO
11 12 13 14
17 19 21 24 23 28 27
[3]
N
F1
+
L
L1
L2
L3
RC
VDC
17 19 21 24 23 28 27
[4]
2
1
VDC
RC
Out
Out
GND
GND
12 11 13 14
L1
L2
L3
OC 2
17 19 21 15 24 23 26 25 28 27
[14]
OC 1
[5]
F1
VDC
VDC
L1
Out
Out
L2
L3
GND
RC
GND
RC
N
12 11 13 14
17 19 21 15 24 23 26 25 28 27
OC 1
L1
L2
17 19 21 24 23 26 25 28 27
[7]
F1
L1
[b]
[c]
[1][2][3][4][5]-
1-phasig, 2 Leiter Anschluß
2-phasig, 3 Leiter Anschluß, 2 Strom-Wandler
3-phasig, 3 Leiter Anschluß, ARON
3-phasig, 3-Leiter Anschluß, ARON und 2 Sp.W.’s
3-phasig, 4-Leiter Anschluß, 4-Leiter,
unsymmetrisch Last, 3 Strom-Wandler
[6]- 3-phasig, 4-Leiter Anschluß, unsymmetrisch Last,
3 Strom-Wandler und 3 Spannungs-Wandler
[7]- 3-phasig, 3-Leiter Anschluß, unsymmetrisch Last, 3 St.W.
[8]- 3-phasig, 3-Leiter Anschluß, unsymmetrisch Last,
3 St.W. und 2 Sp.W.
[9]- 3-phasig, 3-Leiter Anschluß, symmetrisch Last, 1 St.W.
[10]- 3-phasig, 4-Leiter Anschluß, symmetrisch Last, 1 St.W.
und 1 Sp.W.
[11]- 3-phasig, 4-Leiter Anschluß, symmetrisch Last, 1 St.W.
[12]- Stromversorgung Anschluß. Wert der SchmelzSicherung F: Stromversorgung L von 18 bis 60VAC/DC
= 630mA.
H Stromversorgung von 90 bis 260 VAC/DC = 125mA.
[13]- Doppelter Relais-Ausgang
[14]- Doppelter Open Kollektor Ausgang
Der Wert des Last-Widerstands (Rc) muß so sein,
daß der Strom des geschlossenen Kontakt kleiner
als oder gleich 100mA ist. Die VDC Spannung muß
kleiner als oder gleich 30VDC sein.
VDC: äußere Stromversorgung Spannung
OUT: positiver Ausgangskontakt (offener Kollektor
Transistor).
GND: Ausgangskontakt zu Erdung angeschlossen
(offener Kollektor Transistor).
[15]- RS485 Anschluß 4-Leiter [a]- letztes Gerät,
[b]- Geräte 1...n, [c]- RS485/RS232 Umsetzer.
[16]- RS485 Anschluß 2 Leiter [a]- letztes Gerät,
[b]- Geräte 1...n, [c]- RS485/RS232 Umsetzer.
ACHTUNG
• Die Stromeingänge dürfen NUR über Stromwandler angeschlossen werden. Der direkten Anschluß ist nicht möglich.
• Der Anschluß an Erde des Stromwandlers erzeugt
einen Leckstrom von 0 bis 1.8 mA max abhängig von
dem Wert der Eingangswiderstandes, vom Typ des
Anschlußes und der Streckenspannung des Gerätes.
• La connexion à la terre du transformateur de courant produit un courant de dispersion de 0 à 1,8mA max en fonction des valeurs d’impédance d’entrée, du type de
connexion e de la tension de ligne mesurée par l’appareil.
05
GND
05
T
06
T
06
RS485 RS232
RX+
07
RX+
07
TX+
RX-
08
RX-
08
TX-
TX+
09
TX+
09
RX+
TX-
10
TX-
10
RX-
[9]
20 18 27 26
[10]
20 18 27 26
[11]
F1
L2
L3
ATENCIÓN
• Las entradas de intensidad pueden ser conectadas
SOLO por medio de transformadores de intensidad. La
conexión directa no es posible.
• La conexión a tierra del transformador de intensidad
genera una corriente de fuga de 0 a 1,8 mA max. que
depende de los valores de impedancia de entrada, del
tipo de conexión y de la tensión de línea medida por el
instrumento.
20 22 24 27 26
DIN
L1
18
20
22
24
26 27 28 29 30 31
L2
L3
N
F1= 315mA
20 18 27 26
[1]
F1
F1
L1
L1
L2
L3
N
N
20 22 18 27 26 29 28
[2]
[12]
04
02
F1
L1
F
L2
[13]
N
12 13 14 15
20 22 24 27 26 31 30
[3]
F1
FRANÇAIS
L1
[1]- Connexion 1-phase, 2 fils, 1 TC
[2]- Connexion 2 phases, 3 fils, 2 TC
[3]- Connexion 3 phases, 3 fils, ARON
[4]- Connexion 3 phases, 3 fils, ARON et 2 TT
[5]- Connexion 3 phases, 4 fils, charge non-équilibré, 3 TC
[6]- Connexion 3 phases, 4 fils, charge non-équilibré, 3 TC et 3 TT
[7]- Connexion 3 phases, 3 fils, charge non-équilibré, 3 TC
[8]- Connexion 3 phases, 3 fils, charge non-équil., 3 TC et 2 TT
[9]- Connexion 3 phases, 3 fils charge équilibré, 1 TC
[10]- Connexion 3 phases 4 fils, charge équilibré, 1 TC et 1 TT
[11]- Connexion 3 phases, 4 fils, charge équilibré, 1 TC
[12]- Connexion d’alimentation. Valeur du fusible
F: Alimentation L de 18 à 60 VCA/CC = 630mA.
Alimentation H de 90 à 260 VCA/CC = 125mA.
[13]- Double sortie relais
[14]- Double sortie collecteur ouvert
La valeur de la résistance de charge (Rc) doit permettre au courant à contact fermé d’être inférieure à
100mA; la tension VDC: doit être inférieure ou égale à
30 VCC. VDC: tension d’alimentation externe. OUT:
contact positif de sortie (transistor à collecteur ouvert).
GND: contact de sortie connecté à masse (transistor à
collecteur ouvert).
[15]- RS485 connexion 4 fils [a]- dernier appareil,
[b]- Appareil1...n, [c]- convertisseur RS485/RS232.
[16]- RS485 connexion 2 fils [a]- dernier appareil,
[b]- Appareil 1...n, [c]- convertisseur RS485/RS232.
L2
L3
[4]
-
L
+
2
RC
VDC
20 22 24 27 26 31 30
N
1
VDC
RC
Out
Out
GND
GND
13 12 14 15
L1
L2
L3
20 22 24 18 27 26 29 28 31 30
OC 2
[5]
F1
OC 1
[14]
VDC
VDC
L1
Out
L2
L3
GND
Out
RC
GND
RC
N
13 12 14 15
20 22 24 18 27 26 29 28 31 30
[6]
OC 2
ATTENTION
• Les entrées de courant peuvent être connectés SEULEMENT au moyen de transformateurs de courant. La
connexion directe n’est pas permise.
OC 1
L1
L2
[a]
L3
N
PC
20 22 24 27 26 29 28 31 30
[7]
108,5mm
F1
[15]
L1
[b]
[c]
GND
GND
06
GND
06
T
07
T
07
RS485 RS232
RX+
08
RX+
08
TX+
RX-
09
RX-
09
TX-
TX+
10
TX+
10
RX+
TX-
11
TX-
11
RX-
PC
[15]
L2
L3
[a]
GND
GND
05
06
T
06
RS485 RS232
RX+
07
RX+
07
TX+
RX-
08
RX-
08
TX-
TX+
09
TX+
09
RX+
TX-
10
TX-
10
RX-
PC
[16]
96
61.4
91mm
15.4
107.5
mm
mm
≤ 8mm
20 22 24 27 26 29 28 31 30
45
05
T
90
GND
90mm
[8]
[c]
96
17 19 21 24 23 26 25 28 27
[b]
96
[a]
L2
L3
6 7 8 9 10 11 12 13 14 15
[1]- Conexión monofásica , 2 hilos, 1 CT
[2]- Conexión bifásica, 3 hilos, 2 CT
[3]- Conexión trifásica, 3 hilos, ARON
[4]- Conexión trifásica, 3 hilos, ARON y 2 VT
[5]- Conexión trifásica, 4 hilos, carga desequilibrada, 3 CT
[6]- Conexión trifásica, 4 hilos, carga desequilibrada, 3 CT y 3 VT
[7]- Conexión trifásica, 3 hilos, carga desequilibrada, 3 CT
[8]- Conexión trifásica, 3 hilos, carga desequilibrada, 3 CT y 2 VT
[9]- Conexión trifásica, 3 hilos, carga equilibrada, 1 CT
[10]- Conexión trifásica, 4 hilos, carga equilibrada, 1 CT y 1 VT
[11]- Conexión trifásica, 4 hilos, carga equilibrada, 1 CT
[12]- Conexión de alimentación. Valor del fusible F:
alimentación L de 18 a 60 VCA/CC = 630mA.
Alimentación H de 90 a 260 VCA/CC = 125mA.
[13]- Doble salida de relé.
[14]- Doble salida de colector abierto.
El valor de la resistencia de carga (Rc) debe permitir una corriente inferior a 100mA con el contacto cerrado, la tensión VCC debe ser menor o igual
a 30VCC. VDC: tensión de alimentación externa.
OUT: contacto de salida positivo (transistor a
colector abierto). GND: contacto de salida conectado a tierra (transistor a colector abierto).
[15]- RS485 conexión 4 hilos [a]- último instrumento,
[b]- instrumento 1...n, [c]- convertidor RS485/RS232.
[16]- RS485 conexión 2 hilos [a]- último instrumento,
[b]- instrumento 1...n, [c]- convertidor RS485/RS232.
L2
L3
L1
4
L1
GND
GND
2
ESPAÑOL
45mm
[a]
L3
N
[1]- collegamento mono fase, 2 fili, 1 TA
[2]- collegamento bifase, 3 fili, 2 TA
[3]- collegamento 3 fasi, 3 fili, ARON
[4]- collegamento 3 fasi, 3 fili, ARON e 2 TV
[5]- collegamento 3 fasi, 4 fili, carico sbilanciato, 3 TA
[6]- collegamento 3 fasi, 4 fili, carico sbilanciato, 3 TA e 3 TV
[7]- collegamento 3 fasi, 3 fili, carico sbilanciato, 3 TA
[8]- collegamento 3 fasi, 3 fili, carico sbilanciato, 3 TA e 2 TV
[9]- collegamento 3 fasi, 3 fili carico bilanciato, 1 TA
[10]- collegamento 3 fasi, 4 fili, carico bilanciato, 1 TA e 1 TV
[11]- collegamento 3 fasi, 4 fili, carico bilanciato, 1 TA
[12]- collegamento di alimentazione. Valore del fusibile F:
alimentazione L da 18 a 60 VCA/CC = 630mA.
Alimentazione H da 90 a 260 VCA/CC = 125mA.
[13]- Doppia uscita a relè
[14]- Doppia uscita a collettore aperto
Le resistenze di carico (Rc) devono essere dimensionate in modo che la corrente a contatto chiuso
sia inferiore a 100mA; la tensione VDC deve essere minore o uguale a 30VCC. VDC: tensione di alimentazione (esterna). Out: contatto di uscita positivo (transistor a collettore aperto). GND: contatto
di uscita collegato a massa (transistor a collettore
aperto).
[15]- RS485 connessione 4 fili [a]- ultimo strumento,
[b]- strumento 1...n, [c]- convertitore RS485/RS232.
[16]- RS485 connessione 2 fili [a]- ultimo strumento,
[b]- strumento 1...n, [c]- convertitore RS485/RS232.
ATTENZIONE
• Gli ingressi di corrente possono essere collegati SOLO
mediante trasformatori amperometrici. La connessione
diretta non è permessa.
• Il collegamento a terra del TA genera una corrente dispersa da 0 a 1,8mA max. dipendente dai valori di impedenza di ingresso, dal tipo di connessione e dalla tensione di linea misurata dallo strumento.
[6]
OC 2
DEUTSCH
ATTENTION
• The current inputs can be connected ONLY by means of
current transformers. The direct connection is not allowed.
• The connection to ground of the CT produces a leakage current from 0 to 1,8 mA max dependent on the
values of the input impedance, on the type of connection
and on the line voltage measured by the instrument .
[12]
03
01
ENGLISH
[1]- 1 phase 2-wire connection, 1 CT
[2]- 2-phase, 3-wire connection, 2 CT’s
[3]- 3-phase, 3-wire connection, ARON
[4]- 3-phase, 3-wire connection, ARON and 2 VT’s
[5]- 3-phase, 4-wire connection, unbalanced
load, 3 CT’s
[6]- 3-phase, 4-wire connection, unbalanced load, 3 CT’s and 3 VT
[7]- 3-phase, 3-wire connection, unbalanced load, 3 CT
[8]- 3-phase, 3-wire connection, unbalanced load, 3 CT and 2 VT
[9]- 3-phase, 3-wire connection, balanced load, 1 CT
[10]- 3-phase, 4-wire connection, balanced load, 1 CT and 1 VT
[11]- 3-phase, 4-wire connection, balanced load, 1 CT
[12]- Power supply connection. Fuse value F: power
supply L from 18 to 60 VAC/DC = 630mA.
H power supply from 90 to 260 VAC/DC = 125mA.
[13]- Double relay output
[14]- Double open collector output
The value of the load resistances (Rc) must make
the close-contact current be lower than 100mA;
the VDC voltage must be lower than or equal to
30VDC. VDC: Power supply voltage (external).
Out: positive output contact (open collector type transistor). GND: output contact connected to ground
(open collector type transistor).
[15]- RS485 connection 4 wires [a]- last instrument,
[b]- instrument 1...n, [c]- RS485/RS232 transducer.
[16]- RS485 connection 2 wires [a]- last instrument,
[b]- instrument 1...n, [c]- RS485/RS232 transducer.
32.2
50
64.5
L1
L2
L3
[8]
[b]
[c]
GND
GND
06
GND
06
T
07
T
07
RS485 RS232
RX+
08
RX+
08
TX+
RX-
09
RX-
09
TX-
TX+
10
TX+
10
RX+
TX-
11
TX-
11
RX-
PC
[16]