IFM DW3003 Mode d'emploi

PDF
Document
IFM DW3003 Mode d'emploi | Fixfr
/

User questions

G Q

Michael G.

How to set the number of pulses per revolution on the DW3003 control unit?

Access the configuration menu [CFG] and set parameter [PrSC1] to the desired number of pulses per rotation (range 1 to 999). This divides the input frequency to yield the process data value (PDV).

G Q

Michael G.

Which parameter defines the maximum 20 mA scale end point for the analog output on the DW3003?

The parameter [AEP3] (analog end point) defines the maximum scale value corresponding to 20 mA when the output configuration [ou3] is set to current [I].

G Q

Michael G.

What is the function of the [dST.M1] parameter on the DW3003?

The parameter [dST.M1] sets the startup delay for measurement channel MDC1, delaying or suppressing the output signal for the configured duration (range 0.0 to 1000.0).